UMG 512
Mode (delta)
If the difference between two neighbouring sampled
points exceeds the set threshold value, a transient
is detected.
• Off
- Transient monitoring has been switched off.
• Automatic
- Factory default setting. The threshold
value is calculated automatically and is 0.2175 times
the current 200ms effective value.
• Manual
- The transient monitoring uses
the configurable threshold values under "Trns U".
Mode (envelop)
If a sampled value exceeds the envelope range,
a transient is detected.
• Off
- Transient monitoring has been switched off.
• Automatic
- Factory default setting. The envelop
is automatically calculated and is ±5% of the rated
voltage.
• Manual
- The transient monitoring uses the
configurable envelop.
Accepting AUX / MAIN
The transient monitoring can be configured for the
baseline measurement and supporting measurement.
You can accept the settings from the supporting
or baseline measurement.
• No
- The settings from the supporting and baseline
measurement are not accepted.
• Yes
- The settings from the supporting measurement
and baseline measurement are accepted.