Section 5 Programming
Pressing the "Operating mode” key once takes the user from automatic operation to
Programming mode. Parameter 1 ( I-CONVERTER) is reached by pressing "ENTER”.
The upper display always shows the parameter and the lower one the set value. The
values are changed by pressing the
é
/
ê
keys. Subsequent pressing of the "ENTER” key
stores the value and takes the user to the next parameter.
Description of the parameters: See the next page
To quit programming mode in any step, press the "Operating mode” key.
é
é
/
ê
” buttons,confirmation with ENTER)
the automatic test-run is performed.
3 test-runs will be performed during which all stages are being switched on and off. All
necessary parameters are collected, evaluated and stored. Under certain circumstances
3 additional test-runs may be required for a proper initialization.
After successful finalization of AUTO-INIT the controller will switch into normal operation.
In case of recognition of any discrepancies (plausibility) or of inaccurate connection, the
detected error will be displayed in plain text after finalization of AUTO-INIT and can be
eliminated. (see possible error messages at the end of the manual). AUTO-INIT may be
repeated then.
NOTE: If the
Prophi-6R
has been put into operation successfully by AUTO-INIT with all
values unknown, some values will be shown as “????” and this can not be changed. If a
new programming is required, a reset is needed before: Programming/Basic settings
[YES]
5.1. Automatic initialization (not usable in case of external voltage converter)
With the automatic initialization the device will automatically recognize the parameters of
the PFC-system. It also serves as plausibility check and storage of these parameters - the
user only has to make very little or even no adjustments.
Start of the initialization process is done from the menu point “PROGRAMMING” by
pressing the button “ ”
AUTO-INIT [YES] to be confirmed with pressing the ENTER button.
If the values of the current transformer OR the value of the first stage of the PFC-system
are known, they should be entered here. This later enables a display of all values of the
net in the correct electrical term. If no value is programmed (selection: unknown), values
of current and output can later only be indicated as percent.
After entering of the a.m. values (selection via “
- 9 -
1 AUTO - INIT
[ YES ]
1 CURRENT TRANS.
[UNKNOWN]
TEST 3 76 kvar
TEST 1 69 kvar