2.3 Alarm output / error messages
The alarm contact is closed in normal operation and opens in the event of a fault. The
relevant fault is simultaneously shown on the display in plain text (alternating with the
standard display in automatic operation)
UNDER-COMPENSATED
Display and relay output
missing reactive power
OVER-COMPENSATED
Display and relay output
OVERCURRENT
Display and relay output
MEASURING VOLTAGE ?
Display and relay output
OVERTEMPERATURE
Display and relay output
OVERVOLTAGE
Display and relay output
UNDERVOLTAGE
Display and relay output
Section 3 Operating modes
When the operating voltage is switched on, the device briefly displays its designation and
software version, then changes to its normal operating status (automatic operation). The
active cos-phi value is always displayed in the upper line and the currently connected
capacitors are shown as symbols in the lower line (operating display).
HARMONICS
Display and relay output
Additionally several messages for different operation states are generated. An individual
adjustment resp. suppression of particular messages is possible in expert mode 2. During
suppression, the indication of the message in the display, a possible release via alarm-
relays and effects on the controlling process will be prevented.
- 7 -
The power values of the individual capacitors are monitored constantly. If a capacitor is
defective or if the deviation from the rated power is excessive, the
corresponding capacitor is displayed inversely.
Display of active power-line cos phi
Display of “Fan”-option
Active capacitor
branches
Control direction
(here connected-in)
Supply display (for
4-quadrant operation)
The control direction is symbolized
by a closed arrow
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (discharge
time) is running before an impending
switching step
A double arrow symbolizes fast
switching of several branches
Connecting-in
Connecting-out
By pressing the cursor
buttons, the display of
capacitor stages can be
changed:
Display of activated
stages in kvar and in
percent of total output
of PFC system
Display of activated
stages as bar-graph
display in percent of
total output of PFC-
system