Section 14 Technical data
Type series
Outputs
Languages
Switching power of relay outputs
Number of active outputs
Operation and display
Number of control series
User-defined control series
Control principle
Auto-Init
Operating voltage
Measuring voltage
Measuring current
Power drawn
Sensitivity
Target cos phi
Connecting time
Disconnecting time
Discharge time
Fixed stages/ skipped stages
Alarm relay
No-voltage triggering
Display of power-line parameters
Storage of maximum values
Storage of switching number
Storage of operating time
Temperature measurement range
Error memory
Accuracy
Housing
Weight
Operating ambient temperature
Protection type to IEC 60529
Safety guidelines
Sensitivity to interference
(industrial areas)
Prophi-6R
6 (7)
D / E / ES / RU / NL / CZ / PL / F / PT / TR
250 VAC, 1000 W
Programmable
Illuminated graphic display 2 x 16 characters
with convenient operating level
20
1
Sequential connection, loop connection or
self-optimized switching response
Four-quadrant operation
YES
110...230 VAC +/-15%, 50 / 60Hz
30...525 VAC, 50 / 60Hz
X : 5 / 1A selectable
< 5 VA
20 mA / 10 mA
0.1 inductive to 0.1 capacitive adjustable
Selectable from 1 sec ... 20 min.
Selectable from 1 sec ... 20 min.
Selectable from 1 sec ... 20 min.
Programmable
Standard
Standard
Power factor, voltage, apparent current,
frequency, reactive-, active-, apparent power,
missing kvar, temperature, harmonics
Voltage, reactive power, active power, apparent
power, temperature, THD-V, THD-I
Yes, each output, individual reset possible
Yes, each capacitor, individual reset possible
-30°C ... 100°C
Last 40 error states are stored
Current, voltage: 1%
Reactive-, active-, apparent power: 2%
Switchboard-integrated housing
DIN 43 700, 144 x 144 x 53 mm
1 kg
-20 to +60°C
Front: IP 54, Rear: IP 20
IEC 61010-1
IEC 61000-6-2; EN 61326
IEC 61000-4-2: 8kV
IEC 61000-4-4: 4kV