Fault

At target cos phi=1 and inductive load, 

switch-off or connection of capacitor in 

the corrected line 

Supply / Drawing mismatched 

Wrong  line  cos phi  is  displayed

Display:"UNDER CURRENT”

Display: "OVERCURRENT”

Alarm relay: after 10 min.

Display: "UNDERCOMPENSATED”

Alarm relay: after 10 min.

Display: "OVERCOMPENSATED”

Alarm relay: after 10 min.

Display: "MEASUREMENT VOLTAGE ???”

Alarm relay: after 10 min.

Display: "OVERTEMPERATURE”

Alarm relay: after 10 min.

Stages are disconnected for an inductive 

line or connected for a capacitive line 

The  controller  does  not  connect  all 

stages, or cos phi does not change at the 

last stages

In automatic operation, individual stages 

are not connected or disconnected

In strongly asymmetrically loaded lines, 

differences  may  occur  between  control 

r e s p o n s e   a n d   p o w e r - f a c t o r  

measurement,  as  the  power  factor  is 

measured in single phase.

No operating voltage

Check / Solution

Check terminals of the measuring voltage and 

current (l  and  k)!

Check phase position

See above

Current in measuring range?

Line interruption?

Wrong current-converter factor?

Current transformer  short-circuited?

Check current-converter ratio

Go through measuring current range

Check connection and phase position!

All  stages  connected  -  target  cos  phi  not 

reached:  compensation  network  sufficiently 

dimensioned?

Check connection and phase position!

Capacitive grid, although all stages 

disconnected

No measurement voltage!

Cabinet  temperature  too  high:  Outputs  are 

switched off in stages irrespective of power-line 

conditions

If a target cos phi is set which deviates from 1   

despite  an  inductive  line  load,  the  display  < 

(disconnect stages) may light up. The arrows 

indicate the control direction and not the line 

conditions.

Check END STOPP !

Check whether individual stages are 

programmed as fixed stages or OFF in the 

"Manual operation / Fixed stages” menu!

Line  measurements  allow  the  most  favorable 

phase  for  measuring  the  power  factor  to  be 

determined.  The  current  converter  is  set 

accordingly for the measuring current.

Note:  No  display,  alarm  relay  is  activated 

(open)

Section 13  Troubleshooting 

Summary of Contents for Prophi 6R

Page 1: ...lefonischer Support 49 6441 9642 22 E Mail info janitza com www janitza com www janitza com Power Factor Controller Prophi 6R Manual Version 6 0 E 11 2019 Power Factor Controller Prophi 6R Manual 1 2...

Page 2: ...lization 9 5 2 Manual programming 10 5 3 Programming lock 12 Section 6 Manual operation Programming of fixed stages 13 Section 7 Service menu Test run 14 Section 8 Expert mode 15 8 1 Expert mode 1 8 2...

Page 3: ...tion is available which will reduce the commissioning to a minimum Main features R 6 switching outputs 1 alarm relay R Twenty pre programmed control series with a self optimized intelligent control re...

Page 4: ...firm and store values Increase selected parameter Reduce selected parameter 1 2 3 4 5 6 Power Factor Controller Blindleistungsregler Auto Program Manual Service Enter OK Prophi Blindleistungsregler Po...

Page 5: ...e wired with copper leads of 2 2 5mm The connection should be set up as shown in Fig 3 The specified safety regulations must be observed The measuring voltage may lie in the range from 30 525 VAC and...

Page 6: ...d current in the meas system is done in expert mode 1 page 17 Example Meas current L1 Meas Voltage L3 L2 Phase U I 90 6 L1 R L2 S L3 T N Meas current supply voltage Vb meas voltage L2 L3 k l T 2A T 2A...

Page 7: ...t operation states are generated An individual adjustment resp suppression of particular messages is possible in expert mode 2 During suppression the indication of the message in the display a possibl...

Page 8: ...VA ENTER 6 DIFF kVAR TO TARGET COS ENTER 7 FREQUENCY in Hz ENTER 8 TEMPERATURE in C F ENTER 9 HARMONICS 3 19 V I Selection via arrow keys ENTER 10 THD V THD I in ENTER 12 ENERGY in kWh kvarh reset in...

Page 9: ...INIT and can be eliminated see possible error messages at the end of the manual AUTO INIT may be repeated then NOTE If the Prophi 6R has been put into operation successfully by AUTO INIT with all valu...

Page 10: ...ontrol series required for the compensation network is again selected via the keys If the required control series should exceptionally not be present Annex 1 the user may define a special one control...

Page 11: ...40 sec Selection is performed via the keys Continue with ENTER 11 DISCONNECTING TIME This refers to the time between disconnecting the capacitors to reduce the momentary network capacitance Setting r...

Page 12: ...l harmonic distortion THD V is exceeded This value can be set under 27 Harmonics in 15 FAN TEMP 15 70 C Input of the switching threshold for the fan BASIC SETTING NO YES NO When the selection is made...

Page 13: ...ay be permanently defined in succession continued switching via ENTER for the following statuses AUTO Automatic normal operation The relevant output is marked by a capacitor symbol FIXED The output is...

Page 14: ...ER Back to 1 TEST RUN This menu point allows the user to check the settings of the PFC controller After activation of the test run the controller switches each stage on and off successively and calcul...

Page 15: ...values of a measurement can be changed for special applications here 6 SWITCHING POWER max 100 kvar multiples of the smallest stage This factor specifies the maximum power which may be switched in on...

Page 16: ...ified here see point 14 16 TEST ATTEMPTS 5 1 9 When at least this number of successive measurements has resulted in a fault in the capacitor power a C fault message is output 17 OUTPUT 1 STEP 0 255 0...

Page 17: ...rror messages s above Example 3 ALARM DELAY TIME 10 min 1 255min Time after which the alarm relay will respond 4 UNDERVOLTAGE 50 20 100 meas voltage below this threshold will switch OFF all stages at...

Page 18: ...nk Disadvantage This mode can only be used in control series with groups of the same stage power and long settling time as every switching step corresponds to the value of the smallest stage 3 Intelli...

Page 19: ...ored The controller is then set to automatic operation with the operating mode key It is now ready for operation Section 12 Maintenance and warranty The controller should need no maintenance if the op...

Page 20: ...ring voltage and current l and k Check phase position See above Current in measuring range Line interruption Wrong current converter factor Current transformer short circuited Check current converter...

Page 21: ...AC 1000 W Programmable Illuminated graphic display 2 x 16 characters with convenient operating level 20 1 Sequential connection loop connection or self optimized switching response Four quadrant opera...

Page 22: ...s if the required control series is not available for any reason The last control series Control Series E is selected by pressing the Programming key point 4 Control series and confirmed with ENTER Th...

Page 23: ...rations warning Fast discharge Phase shift U I C Test C Fail Test Attempts Power 1 stage Control Default setting ENGLISH 1000 A 5 A 6 1 INTELLIGENT 25 00 kvar 0 98 IND 230 V L N NO 40 sec 40 sec 60 se...

Page 24: ...Prophi 6R 24 24...

Page 25: ...ME 60 s 13 ALARM TEMP 55 C 14 MESSAGE RELAY FAN 15 FAN TEMP 30 C 8 TEMPERATURE 25 0 C 9 HARMONICS 3 V 0 5 I 0 1 10 HARMONICS THD V 0 5 I 0 3 11 SYSTEM POWER 88 88 kvar 12 ENERGY 88 88 kWh SOFTWAREVERS...

Page 26: ...SAT UNDERCOMPENSAT HARMONICS OVERTEMPERATURE OVERCURRENT UNDERVOLTAGE SWITCH OPERATIONs MEAS CURRENT C1 AUTO FIXED OFF C2 AUTO FIXED OFF C3 AUTO FIXED OFF C4 AUTO FIXED OFF C5 AUTO FIXED OFF C6 AUTO F...

Page 27: ...Prophi 6R 27...

Page 28: ...Janitza electronics GmbH Vor dem Polst ck 6 D 35633 Lahnau Tel 49 6441 9642 0 E Mail info janitza de info janitza de www janitza de...

Reviews: