Module 96-PA-RCM / 96-PA-RCM-EL
www.janitza.de
52
General
Net weight of
module
(with attached plug-in connectors)
78 g (0.17 lbs)
Impact resistance
IK07 according to IEC 62262
Transport and storage
The following specifications apply for devices transported and stored in the original packaging.
Free fall
1 m (39.37 in)
Temperature
K55
-25° C (-13 °F) to +70° C (158 °F)
Relative air humidity (non-condensing)
0 to 90% RH
Environmental conditions during operation, see the usage information for your basic device.
Analog inputs
Differential or current signals
2x
Temperature measurement
1x
Residual current input
Nominal current
30 mA
rms
| 0...20 mA | 4...20 mA
Measuring range
0 .. 30 mA
rms
Operating current
50 µA
Resolution
1 µA
Cable break detection (failure monitoring)
Can be activated
Crest factor
1.414 (relative to 30 mA)
Load
4 Ω
Overload for 1 s
1 A
Constant overloaded
200 mA
Measurement of residual currents
According to IEC/TR 60755 (2008-01):
Type A
Type B and B+
Temperature measurement
Update time
200 ms
Suitable thermal sensor
PT100, PT1000, KTY83, KTY84
Total burden (thermal sensor and lead)
max. 4 kΩ
Thermal sensor
type
Temperature range
Resistance range
Measurement uncer-
tainty
PT100
-99 °C (-146.2 °F) ... +500 °C (932 °F)
60 Ω ... 180 Ω
±1.5% rng
PT1000
-99 °C (-146.2 °F) ... +500 °C (932 °F)
600 Ω ... 1.8 kΩ
±1.5% rng
KTY83
-55 °C (-67 °F) ... +175 °C (347 °F)
500 Ω ... 2.6 kΩ
±1.5% rng
KTY84
-40 °C (-40 °F) ... +300 °C (572 °F)
350 Ω ... 2.6 kΩ
±1.5% rng
11. Technical data for the module
11.1 Technical data