66
Turnover Limit
Only appears for As Turns. Enter the maximum number of
turnovers. The controller can activate an alarm when this number has been exceeded.
Set Turnover Value
Only appears for As Turns. Enter the current number of turnovers if you are not starting
with a fresh bath (otherwise reset total to zero, see below).
Reset Total
Enter this menu to reset the accumulated time, volume, or metal turnovers, to zero.
Touch Confirm to accept, Cancel to leave the total at the previous value and go back.
Input
Select the sensor to be used by this relay.
Control
Select the control direction.
5.3.4
Plating Follow
Plating Follow is commonly used to feed pH adjustment, reducing agent and/or stabilizer in proportion to electro-
less copper or nickel replenishment. The Plating Follow relay will activate at the same time as the assigned Control
relay, for the same amount of time.
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, accumulated on-
time, total feed volume (if enabled), alarms related to this output, relay type and the current control mode setting.
Settings
Touch the Settings icon to view or change the settings related to the relay.
Total Mode
Enter this menu to select the method and program feed totalization
Pump Capacity
Only appears for As Volume. Enter the maximum feed rate of the pump connected to
this relay.
Pump Setting
Only appears for As Volume. Enter the stroke length setting for the metering pump, in
percent
Reset Total
Enter this menu to reset the accumulated time, or volume, to zero. Touch Confirm to
accept, Cancel to leave the total at the previous value and go back.
Control
Select the relay to be used to activate this relay.
5.3.5
Relay, Percent Timer Control Mode
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, cycle time, accumulated
on-time, alarms related to this output, current cycle on time, relay type and the current control mode setting.
Settings
Touch the Settings icon to view or change the settings related to the relay.
Sample Period
Enter the duration of the sample period.
Feed Percentage
Enter the % of the sample period time to use for the feed relay activation time
5.3.6
Relay, Alarm Output Mode
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, accumulated on-
time, alarms related to this output, current cycle on time, relay type and the current control mode setting.
Settings
Touch the Settings icon to view or change the settings related to the relay.