64
Input
Select the physical input whose raw value will be used as this virtual input.
Smoothing Factor
Increase the smoothing factor percentage to dampen the response to changes. For ex-
ample, with a 10% smoothing factor, the next reading shown will consist of an average
of 10% of the previous value and 90% of the current value.
Name
The name used to identify the input may be changed.
Type
Select the type of input; either Calculation, Raw Value, or Not Used
5.3 Outputs Menu
Touch the Outputs icon from the Main Menu to view a list of all relay and analog outputs. The Page Down icon pages down
the list of outputs, the Page Up icon pages up the list of outputs, the Main Menu icon brings back the previous screen.
Touch an output to access that output’s details and settings.
NOTE: When the output control mode or the input assigned to that output is changed, the output reverts to OFF mode.
Once you have changed all settings to match the new mode or sensor, you must put the output into AUTO mode to
start control.
5.3.1
Relay, Any Control Mode
Settings
Touch the Settings icon to view or change the settings related to the relay. Settings that are available for any control
mode include:
HOA Setting
Select Hand, Off or Auto mode by touching the desired mode.
Output Time Limit
Enter the maximum amount of time that the relay can be continuously activated.
Once the time limit is reached, the relay will deactivate until the Reset Output
Timeout menu is entered.
Reset Output Timeout
Enter this menu to clear an Output Timeout alarm and allow the relay to control the
process again.
Interlock Channels
Select the relays and digital inputs that will interlock this relay, when those other
relays are activated in Auto mode. Using Hand or Off to activate relays bypasses
the Interlock logic.
Activate With Channels
Select the relays and digital inputs that will activate this relay, when those other
relays are activated in Auto mode. Using Hand or Off to activate relays bypasses
the Activate With logic.
Minimum Relay Cycle
Enter the number of seconds that will be minimum amount of time that the relay
will be in the active or inactive state. Normally this will be set to 0, but if using a
motorized ball valve that takes time to open and close, set this high enough that the
valve has time to complete its movement.
Hand Time Limit
Enter the amount of time that the relay will activate for when it is in Hand mode.
Reset Time Total
Press the Confirm icon to reset the total accumulated on-time stored for the output back to 0.
Name
The name used to identify the relay may be changed.
Mode
Select the desired control mode for the output.
5.3.2
Relay, On/Off Control Mode
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, accumulated on-
time, alarms related to this output, current cycle on time, relay type and the current control mode setting.
Settings
Touch the Settings icon to view or change the settings related to the relay.