Page 48
Operation and Maintenance
Envistar Flex
DSEF191101.05.EN
Continuous product development may give rise to specification changes without notice.
6.10 Dampers (code ESET-TR, EMT-01)
Dampers
may have different functions and be positioned in different places.
• EMT-01 shut-off/ regulated damper
• ESET-TR trim damper with manual control
The purpose of the dampers is to regulate the air flow. Faulty function gives rise to
disturbances that may result in serious problems.
- If the damper does not open fully, the air flow is reduced.
- If the damper leaks, this will result in increased energy use.
- If the trim damper for the rotor purging function is not working or is incorrectly set,
it may result in odours from the extract air being transferred to the supply air via the
rotor.
- If the damper is placed on the outdoor air side and does not close completely when
the unit stops, the heating coil may freeze.
Inspection
DANGER!
Risk of serious personal injury and/or damage to air handling unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
1. Check the function of the damper actuator.
2. Check the dampers for tightness when they are closed. If they are not sealed,
adjust the damper actuator to make the dampers tight (does not apply to trim
dampers).
3. Check the sealing strips.
4. If the damper is not working, check that there are no screws penetrating the drive
mechanism/damper blades to interfere with damper function.
Cleaning
DANGER!
Risk of serious personal injury and/or damage to air handling unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
Clean the damper blades with a cloth. In the event of heavy soiling, an environmentally
friendly degreasing agent can be used.