Page 37
Operation and Maintenance
Envistar Flex
DSEF191101.05.EN
Continuous product development may give rise to specification changes without notice.
Cleaning
DANGER!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
If the fins on the coils are dirty, vacuum them from the inlet side. Alternatively,
you can blow them clean with compressed air from the outlet side. If they are
particularly dirty, clean them with hot water mixed with dishwashing detergent
(that will not corrode aluminium).
Bleeding
DANGER!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
Bleed the heating coil and the pipework if needed. Bleeder screws are on top of
the coils or on the pipe connections.
Function
DANGER!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
EXP
CP3
GT9
SV3
CP3
SV3
GT9
Supply air fan
Extract air fan
Circulation pump energy recovery circuit
Valve actuator energy recovery circuit
Freezing sensor
SF
EF
SF
EF
Check that the circulation pump is running in the correct direction and that the
valve changes to opening/closing when the setpoints/conditions are changed.