Page 51
Operation and Maintenance
Envistar Flex
DSEF191101.05.EN
Continuous product development may give rise to specification changes without notice.
6.13 Recirculating unit with shut-off/regulated damper (code EBE)
The recirculating unit with shut-off/regulated damper is used to, for example,
recirculate air in conjunction with heating of the premises at night.
Inspection
DANGER!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
1. Check the function of the damper actuator.
2. Check the dampers for tightness when they are closed. If they are not sea-
led, adjust the damper actuator to make the damper tight.
3. Check the sealing strips.
4. If the damper is not working, check that there are no screws penetrating the
drive mechanism/damper blades to interfere with damper function.
Cleaning
DANGER!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
Clean the damper blades with a cloth. If they are severely fouled, an environme-
ntally friendly degreasing agent can be used.