Page 31
Operation and Maintenance
Envistar Flex
DSEF191101.05.EN
Continuous product development may give rise to specification changes without notice.
- Read the recommended setting (adjustment hole in the purging sector) from
the table below.
Rotor vari-
ant
Adjustment hole in the purging sector
5
open*
4
3
2
1
closed
Diff. pressure
between P1 and
P3 (Pa)
NO, NE,
HY, HE, EX
< 200
200 – 400 400–600
> 600
–
NP, NX, HP
< 300
300–500
500–700
> 700
–
*
maximum open purge sector, preset position from the factory
- Adjust the purging sector if the need arises. The illustration shows the
purging sector set to the maximum open position.
Outdoor
air
Supply
air
Direction
of rotation
Extract
air
Exhaust
air