background image

User manual iSMA-B-AAC20/M-Bus Network 

 

Version 1.2 

             www.globalcontrol5.com 

Page 5 / 13

 

  

 

Figure 2 M-Bus connection topology 

A two-wire cable (jYStY N*2*0.8 mm) is used as the transmission medium for the M-Bus. 
The  maximum  distance  between  the  slave  and  the  repeater  is  350  m;  this  length 
corresponds  to  a  cable  resistance  of  up  to  29 

.  This  distance  applies  for  the  standard 

configuration having a baud rate between 300 and 9600 baud rate, and a maximum of 250 
slaves. The maximum distance can be increased by limiting the baud rate and using fewer 
slaves, but the bus voltage in the Space state must at no point in a segment fall below 12 V, 
because of the remote powering of the slaves. In the standard configuration, the total cable 
length  should  not  exceed  1000  m,  in  order  to  meet  the  requirement  of  a  maximum  cable 
capacitance of 180 nF. 

 

3.2 M-Bus Addressing 

The M-Bus devices are using two types of addressing: 

 

Primary: This address is assigned by the user in a commissioning process (all new M-

Bus  devices  have  this  address,  set  by  the  factory  to  0);  this  type  of  address  has  a 
limited range from 0 to 250; 

 

Secondary:  This address has  a wider range than primary and  by default contains  a 

device  serial  number.  All  out  of  box  devices  connected  to  the  bus  have  unique 
secondary addresses.  
 

4 M-Bus Kit Components 

The M-Bus kit contains two types of device components based on communication interface: 

 

Local Device: for devices connected directly to the iSMA-B-AAC20-M (this connection 

requires a special hardware version equipment with the M-Bus interface). This type of 
communication is using two components: 

 

MbusLocalNetwork: The main component responsible for handling local interface, 

 

MbusLocalDevice: The component responsible for handling devices connected to 
the local interface; 

Summary of Contents for B-AAC20

Page 1: ...iSMA B AAC20 User Manual M Bus Network Global Control 5 S A Warsaw Poland www globalcontrol5 com ...

Page 2: ...s Kit 3 2 1 Installation of the iSMA M Bus Kit 3 3 About M Bus 4 3 1 M Bus Topology and Cable 4 3 2 M Bus Addressing 5 4 M Bus Kit Components 5 5 M Bus Local Network Component 6 6 M Bus Local Device 7 6 1 M Bus Local Device Points 9 7 M Bus IP Network 9 8 M Bus IP Device 11 8 1 M Bus IP Device points 13 ...

Page 3: ...k components 1 2 27 01 2020 Replaced environment of programming from Workplace to iSMA Tool Table 1 Revision history 2 M Bus Kit To serve the M Bus protocol connected either to the Local interface or by the IP gateway the iSMA B AAC20 controller uses the iSMA_MBus kit 2 1 Installation of the iSMA M Bus Kit To install the M Bus kit import the kit to the iSMA Tool software possibly as part of the pa...

Page 4: ...driven systems including consumer utility meters When interrogated the meters deliver the data they have collected to a common master for example a DDC controller or a hand held computer connected at periodic intervals to read all utility meters of a building 3 1 M Bus Topology and Cable The M Bus is a hierarchical system with communication controlled by a master for example the iSMA B AAC20 M The...

Page 5: ...quirement of a maximum cable capacitance of 180 nF 3 2 M Bus Addressing The M Bus devices are using two types of addressing Primary This address is assigned by the user in a commissioning process all new M Bus devices have this address set by the factory to 0 this type of address has a limited range from 0 to 250 Secondary This address has a wider range than primary and by default contains a devic...

Page 6: ...al Network Component This component is responsible for servicing the M Bus devices connected directly to the iSMA B AAC20 M M Bus interface The max number of devices connected to the iSMA B AAC20 is 20 and it is a hardware limitation a built in M Bus power supply Figure 3 M Bus Local Network property sheet view This component has the following actions Search Primary Address Discovers devices conne...

Page 7: ...ll frequency Normal Rate Time between device read in Normal mode poll frequency Slow Rate Time between device read in Slow mode poll frequency Read Trigger Remote force device data read trigger Average Poll Time Average time for sending receiving one message Busy Time Percentage of the M bus network usage Total Polls Total number of messages Fast Polls Number of messages sent in Fast mode Normal P...

Page 8: ... the Primary Address All new devices have factory default Primary Address set to 0 WARNING ALL discovered devices are placed in the DiscoveredDevices folder In this folder devices are read only for normal use they must be moved from this folder and placed directly to another MbusFolder under the MbusLocalNetwork component Figure 4 M Bus Local Device property sheet view This component has the follo...

Page 9: ...rigger Remote force device data read trigger Baud rate Device read baud rate available options 300 600 1200 2400 4800 9600 19200 38400 6 1 M Bus Local Device Points The iSMA_Mbus kit does not have device points components available in the Sedona Palette for the user s use The devices points are added automatically during the points discovery process In the discovery process the response message is...

Page 10: ...t Primary Address set to 0 it is recommended to search by the Secondary Address for new devices Search Secondary Address Discover devices connected to the M Bus Local interface by Secondary Address This address contains part of the device serial number and is assigned in the factory This action is recommended for the first bus commissioning Read Network Force devices data read Reset Stats Reset ne...

Page 11: ... port number Parameters like Retry Count Initialization Delay Response Timeout and Inter Message Delay are used in the device discovery action If it is required these parameters can have different settings in devices than the network devices connected to the bus can have different communications parameters 8 M Bus IP Device The M Bus IP Device is a component for servicing the M Bus devices connect...

Page 12: ...ification The component has the following slots Status Component s current status Fault Cause Fault cause description Enabled Enables Disables the M Bus IP Device Last Read Success Last proper success device read time Poll Frequency Device read frequency times defined in the network component Address Mode Defines the device communication type address Primary or Secondary Primary Address Device Pri...

Page 13: ... components available in the Sedona Palette for the User s use The device points are added automatically during the points discovery process In the discovery process response message is decoded and based on this information the iSMA B AAC20 creates corresponding points components The iSMA_Mbus kit uses two types of components Numeric for numeric values String for values other than numeric like des...

Reviews: