User manual iSMA-B-AAC20/M-Bus Network
Version 1.2
www.globalcontrol5.com
Page 10 / 13
Figure 5 M-Bus IP Network property sheet view
This component has the following actions:
Search Primary Address: Discovers devices connected to the M-Bus Local interface by the
Primary Address.
The user can also enter the searching range in action pop-up window by doing a simple
calculation: Range Number = Start Address * 256 + End Address, for example, to search a
range from 10 to 20 the user must enter 2580 (10*256 + 20=2580).
WARNING! All new devices have the default Primary Address set to 0, it is recommended to
search by the Secondary Address for new devices.
•
Search Secondary Address: Discover devices connected to the M-Bus Local interface by
Secondary Address. This address contains part of the device serial number and is
assigned in the factory. This action is recommended for the first bus commissioning.
•
Read Network: Force devices data read,
•
Reset Stats: Reset network statistic and start calculating from 0.
The component has the following slots:
•
Status: Component
’s
current status;
•
Fault Cause: Fault cause description;
•
Enabled: Enables/Disables the M-Bus Local Network;
•
Last Discovery Time: Last success discovery action time;
•
Retry Count: Max. number of error messages (CRC error, lost messages) before device
down;