STATUS FLAG Property
The Status Flag property contains information about the status of object status. This
property consists of 4 binary flags. Each flag is described in the table below.
Module Input
Results
TO Switch
Priority Array
Present Value
Digital Output
Status Flag Property
Auto position
NULL
Default
Default
0000
BINARY VALUE
BINARY VALUE
BINARY VALUE
Manual position
ON
null
TRUE
ON
0010
ON
Manual position
OFF
null
FALSE
OFF
0010
OFF
Table 27. STATUS FLAG property changes
8.5.2 TO PWM VALUE - Triac PWM Object Description (Analog Output:
0-3)
This object is designed to serve the triac output in the PWM mode. The BACnet PWM
VALUE object has the following properties:
Dynamically creatable: no, dynamically deletable: no.
Property
Name
Require
d
Proprietar
y
Writable
Property
ID
Data Type
Description
OBJECT_IDENTI
FIER
Yes
From AO:0 to AO:3
OBJECT_NAME
Yes
TO-x PWM VALUE
OBJECT_TYPE
Yes
PRESENT_VALU
E
Yes
Yes
PRESENT_VALUE Property
STATUS_FLAGS Yes
STATUS FLAG Property
EVENT_STATE
Yes
OUT_OF_SERVI
CE
Yes
Yes
OUT OF SERVICE Property
UNITS
Yes
PRIORITY_ARRA
Y
Yes
Yes