iSMA-B-MINI/MIX BACnet User Manual
www.ismacontrolli.com
DMP261en | 1st Issue rev. 8 | 05/2022
page 40 of 114
7.2 VALID_FRAMES_FOR_US_CNT Property 5101
The property contains the number of valid frames (on the MS/TP layer) addressed to this
module.
7.3 VALID_FRAMES_FOR_NOT_US_CNT Property 5102
The property contains the number of valid frames (on the MS/TP layer), which are not
addressed to this module.
7.4 ERROR_FRAMES_CNT Property 5103
The property contains the number of invalid frames on the MS/TP layer.
7.5 TRANSMITTED_FRAMES_CNT Property 5104
The property contains the number of transmitted frames.
7.6 UP_TIME Object (Analog Value: 0)
The object shows the time of module operation module (expressed in seconds) from the
last power-up or the module reset.
7.7 WATCHDOG Object (Analog Value: 1)
The object specifies the time (expressed in seconds) to watchdog reset. If the module
does not receive any valid BACnet message within that time, all PRIORITY_ARRAYs will be
set to null, and the PRESENT_VALUE for outputs will be set to the RELINQUISH_DEFAULT
value.
This feature is useful in case of an interruption in data transmission, and if, for security
reasons, output states must be set to the appropriate state in order to avoid endangering
the safety of persons or the property.
The default value is 0 seconds, which means the watchdog function is disabled. To
maintain the compatibility, this object is also available as the Device object property 5001.
If the watchdog is triggered, the power LED blinks with the specified sequence (3 blinks
with 20 Hz frequency and 1-second pause).
7.8 FIRMWARE VERSION AND MODULE TYPE Property 3030
The property contains the type and firmware version of a module.
The low byte contains information about a type of a module in accordance with the table
below:
Value
Type
81
10
(0x51
16
)
8I
91
10
(0x5B
16
)
8I-IP
84
10
(0x54
16
)
8U