iSMA-B-MINI/MIX BACnet User Manual
www.ismacontrolli.com
DMP261en | 1st Issue rev. 8 | 05/2022
page 52 of 114
Module Input
Results
DO Switch
Priority Array
Present Value
Digital Output
Status Flag Property
Auto position
NULL
Default
Default
0000
BINARY VALUE
BINARY VALUE
BINARY VALUE
Manual position
ON
NULL
TRUE
ON
0010
BINARY VALUE
Manual position
OFF
NULL
FALSE
OFF
0010
BINARY VALUE
Table 24. STATUS FLAG property changes
OUT OF SERVICE Property
For digital outputs, the OUT OF SERVICE property is set to true if the output is overridden
by the USB connection or from a module web page (only in IP version). In such case, the
OUT OF SERVICE is set to false if the Present Value property is set by the BACnet
message.
8.4.2 HAND_STATUS Object (Multistate Value: 23-26)
The property stores information about the status of the hand operation switch and the
status of the DO in the hand mode, according to the table below:
Value of Hand Status
Status Description
1
AUTO-OUT=OFF
2
AUTO-OUT=ON
3
PWM
4
HAND-OUT=OFF
5
HAND-OUT=ON
Table 25. The HAND STATUS object value list
8.5 Triac Output BACnet Objects
8.5.1 TO - Triac Output Object Description (Binary Output: 0-3)
The object is designed to service the triac output working in the digital mode. The BACnet
Triac Output object has the following properties:
Dynamically creatable: no, dynamically deletable: no.