iSMA-B-MINI/MIX BACnet User Manual
www.ismacontrolli.com
DMP261en | 1st Issue rev. 8 | 05/2022
page 48 of 114
type object, therefore additional objects have been created for the counters. The Analog
Value has one
drawback–
odd values above 16777216 are rounded down by 1. For
example, 16777216 + 1 is still displayed as 16777216, but 16777216 + 2 is displayed
properly as 16777218.
8.3 Analog Output BACnet Objects
8.3.1 AO - Analog Output Object Description (Analog Output: 0-5)
Each of the analog outputs in all types of modules is represented on the BACnet network
as the BACnet Analog Output object with the following properties.
Dynamically creatable: no, dynamically deletable: no.
Property
Name
Required
Proprietary
Writable
Property ID
Data Type
Description
OBJECT_IDENTIFI
ER
Yes
From AO:0 to AO:5
OBJECT_NAME
Yes
AO-x
OBJECT_TYPE
Yes
PRESENT_VALUE
Yes
Yes
PRESENT_VALUE
property
STATUS_FLAGS
Yes
STATUS FLAG
property
EVENT_STATE
Yes
OUT_OF_SERVIC
E
Yes
Yes
OUT OF SERVICE
property
UNITS
Yes
PRIORITY_ARRAY
Yes
Yes
RELINQUISH_DE
FAULT
Yes
Yes
COV_INCREMEN
T
no
Yes
COV INCREMENT
property
OUTPUT_TYPE
*
Yes
Yes
4001
Enumerated
HAND_STATUS
*
Yes
3014
Boolean
HAND_VALUE
*
Yes
3015
Enumerated
Table 19. Properties of the Analog Output object