iES6 Series User’s Manual
iS5 Communications Inc.
14
3.4
Power Connections
The iES6 and iES6-S Series Ethernet switch supports 3 different dual redundant power supplies (PWR1 and
PWR2):
1.
LV: Dual Input 10-48VDC
2.
MV: Dual Input 36-75VDC
3.
HV: Single Input 85-264VAC or 88-370VDC with a Single 10-48VDC Backup.
Figure 8 - Power Connection
The label on the terminal block will indicate the accepted voltage range for PWR1 and PWR2. Positions 2,
4 and 6 are all for ground connections (connected via a removable jumper) and can be used for any ground
connection. The 3 tables below list the power connections for each type of input power.
The Phillips Screw Terminal Block has Phillips screws with compression plates, allowing either bare wire
connections or crimped terminal lugs. The use of #6 size ring lugs is recommended to ensure secure and
reliable connections under severe shock or vibration. The terminal block comes with a safety cover which
must be removed before connecting any wires. This cover must be re-attached after wiring to ensure
personnel safety.
1.
LV: Dual Input 10-48VDC
Terminal
Number
Description
Connection
1
PWR1 (+) : Positive
Connected to the positive of the 1
st
10-48VDC power
source.
2
PWR1
: Ground
Power supply 1 ground connection.
3
PWR1 (-) : Negative
Connected to the negative of the 1
st
10-48VDC power
source.
4
: Chassis Ground
Connected to the safety ground terminal for AC Units or
the ground bus for DC inputs. Chassis Ground connects to
both power supply surge grounds via a removable jumper.
5
PWR2 (+) : Positive
Connected to the positive terminal of the 2
nd
10-48VDC
power source.
6
PWR2
: Ground
Power supply 2 ground connection.