iPOWER TPD-800A User Manual
23
Humidity rating: 0%~100%;
Current rating: 0~-10A
H. TIMING
"SEG TIMING" adjust the device time, set the time of device power on/off
Command line input format: SEG TIMING
【
ADDRESS
】【
OPTION
】
【
ADDRESS
】
: the series number of connected device
【
OPTION
】
as detailed in Figure 3-6-h:
Figure 3-6-h the description table of TIMING OPTION
♦
Adjust the time:
SET TIMING
【
ADDRESS
】
CHECK=091231042150
The format of the time: year-month-day-week-hour-minute, each section with 2 digits, 24-hour clock
Week reference table
week
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Command
line
01
02
03
04
05
06
00
♦
The time setting of output
Command line input format: SET TIMING
【
ADDRESS
】
1 Y ON=0912301456
1
:
the outlet No.
Y
:
daily timing repeat , Y means repeat, N means non-repeat
ON
:
the status of switch on/off, ON means power on, OFF means power off
=0912301456
:
the time of power on/off, format: year-month-day-hours-minute, each section with 2 digit, 24-hour
clock.
Note:
"NULL" can clear the setting information
I)
ONINTERVAL
"SET ONINTERVAL" set the interval of the device sequential power on
【
OPTION
】
Description
CHECK
Adjust the device time
NO
Set the time of each individual output