Technical data
Page 7
Operating manual LC 340.01-A.3.5/6
Current revision status: Apr 4, 2019
3 Technical Data
3.1 General data
Type:
LC 340.01-A.3.5/6
Electric drawing:
P35-001340
Mechanical drawing:
P20-000165
3.2 Refrigerant circuit
Type of refrigerant:
R407C
Refrigerant filling:
kg
7.0
Maximum pressure:
bar
28
3.3 Dimension and weight water module
Footprint:
Depth:
mm
1093
Width:
mm
815
Height:
mm
1952
Additional depth electrical cabinet:
Depth:
mm
211
Width:
mm
500
Weight:
Without water filling:
kg
480
With water filling:
kg
600
3.4 Operating voltage 460 V / 3 Phase / 60 Hz
Design point:
Cooling capacity:
kW
38.8
Heat load to the air:
kW
52.2
Air inlet temperature:
°C
+ 33
Air flow:
m³/h
12000
Operating limits:
Max. air inlet temperature:
°C
+ 40
Min. air inlet temperature:
°C
+ 10
Min. water flow evaporator:
l/min
44
Max. storage temperature:
°C
+ 64
Min. storage temperature:
°C
- 40 (without water)
Electrical data:
Power consumption @ design point:
kW
21.0 (without tank heaters)
Max. power consumption:
kW
24.9
Connecting voltage:
460 V / 3 Ph / PE
Voltage tolerance:
%
+/- 10
Frequency:
Hz
60
Control voltage:
VDC
24