Maintenance work
Page 35
Operating manual LC 340.01-A.3.5/6
Current revision status: Apr 4, 2019
Warning indication:
Warning lamp
“Warnings / Water temperature”
is lighting yellow.
Action:
This message will not influence the chiller operation. It is only a warning message that
a temperature value is near limit.
Please check page
“Events”
in LaserNet for further information.
a) Tap water temperature near limit
Tap Water Temperature
T(MIN):
18.0°C
T(MAX):
26.0°C
Hysteresis:
0.5°C
Following conditions will activate this warning message:
-
Tap water temperature between 18 and 18.5°C (near minimum limit)
-
Tap water temperature between 25.5 and 26°C (near maximum limit)