64
Figure 4-23 Warning screen
Setup-System setting list is shown in
Table 4-8
.
Table 4-8
: Setup-System setting list
Setting Item Sub Item
Explanation
Output
Voltage
--
Set output voltage
220Vac (Default)
230Vac
240Vac
MUST be reviewed after UPS installation
BYPASS
SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper limit
+10%
+15% (Default)
+20%
Lower limit
-10%
-20% (Default)
-30%
Bypass Frequency
Range
Set bypass Frequency range:
Upper/ Lower limit
+/- 1Hz
+/- 2Hz
+/- 4Hz (Default)
Converter
Mode
--
Set converter mode
Disable (Default)
Enable
ECO Mode
--
Set ECO mode
Disable (Default)
Enable
Bypass
Mode
--
Set bypass mode
Disable (Default)
Enable
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please
enable it.