RBU100H operation manual
6 Function parameters
-21-
6.2 Detailed function
Function code
Name
Detailed instruction
Default
P0.00
Control mode
0
–
1
0: Keypad
1: Terminal
S1 valid: automatic operation
S2 valid: manual operation
1
P0.01
Keypad control
0
–
1
0: Automatic operation
1: Manual operation
0
Automatic operation:
In automatic operation, the RBU detects the DC voltage and the operation stops.
The RBU works when DC voltage of the VFD-standard DC voltage
>
P0.04
The RBU stops when DC voltage of the VFD-standard DC voltage
<
P0.05
Manual operation:
RBU works when receiving the command.
Operation state of RBU
Command of manual operation
About 1 second
DC voltage of the inverter
Energy regenerative
Valid
Run
Run
AC voltage x1.35
Regenerative current
Inverter state