4 Installation guidelines
-14-
2) Select P0.00=1 (terminal control);
3) Set as manual mode (S2 valid).
R
S
T
U
V
W
R
S
T
R
S
T
r
s
t
S1
S2
S3
S4
COM
24V
S1
S2
S3
S4
COM
24V
Y
COM
M
Power supply
VFD
RBU
Input filter
Input
reactor
Regenerative
reactor
Regenerative
reactor
RBU
Master
Slave
PE
CN9
AO
GND
ROB
ROA
ROC
Y
COM
CN9
AO
GND
ROB
ROA
ROC
PE
r
s
t
PE
(+)
(-)
(+)
(-)
(-)
(+)
PE
It is recommended to
use fuse
It is
recommended
to use fuse
Figure 4-7 Parallel connection 1 of RBU100H
Connection instruction: make the first RBU as the master and others as the slave in parallel
connection. Connect the Y and COM terminal of the first RBU to the S2 and COM terminal of the
second one, third one and so on.
Note:
RBU 380V 22kW
–45Kw has internal output reactor. RBU 380V 55kW–250kW/660V
55kW
–400kW has standard output reactor.
Each RBU100H has 1 standard input reactor. Select the input reactor according to the rated
parameters of the VFD.
The input filter is optional. Select the input filter according to the rated parameters of the VFD.
The fuse is optional. Configure the fuse at 1.5 times of the rated current of the RBU.
Derate 90% of the RBU100H in parallel connection.