4 Installation guidelines
-11-
4.4 Terminals and function
4.4.1 Terminals of the main circuit
(
+
)
(
-
)
R S
T
r
s
t
Figure 4-3 Terminals of the main circuit
The main circuit of RBU100H is very simple. Connect the terminals "(+)" and "(-)" of the RBU to the
positive and negative poles of the VFD; connect the terminals "R", "S" and "T" of the RBU to the
power supply of the VFD input end directly or by means of output reactor; connect the terminals "r",
"s" and "t" of the RBU to the grid.
It is necessary to use an external reactor on RBU100H (the RBU of 380V
22
–45kW has internal reactor). The reactor terminals must match the RBU
terminals; otherwise the damage to RBU and fire may occur.
Note the polarity of the RBU; otherwise the damage to RBU and fire may
occur.
The "r", "s" and "t" of the RBU connect to 3PH power terminals "R", "S", and
"T" respectively (see Figure 4-5 and Figure 4-6). Otherwise, breaker tripping
or RBU fault or even damage may occur.
Ground the PE terminal of the RBU to avoid physical injuries.
4.4.2 Terminals of the control circuit
ROA ROB ROC
AO GND S1 S2 S3 S4 COM +24V Y
Figure 4-4 Terminals of the control circuit
Terminal
Function
S1
–S4
ON-OFF input terminal. Optical coupling isolation input terminal with +24V
and COM.
S1: Valid in terminal control. Automatic input.
S2: Valid in terminal control. Automatic/Manual input.
S3: Multi-function terminal
S4: Multi-function terminal
Y
Open collector output terminal, the corresponding common ground terminal
Terminal
Function
r, s, t
Terminals of 3-phase AC input (see Figure 4-5 and Figure 4-6)
(+), (-)
Input terminals of RBU
R, S, T
Terminals of external DC reactor or VFD (see Figure 4-5 and Figure 4-6)
Grounding terminal (PE)