RBU100H operation manual
4 Installation guidelines
-15-
4.6.2 Parallel connection of RBU100H (No master and slave)
R
S
T
U
V
W
R
S
T
R
S
T
r
s
t
S1
S2
S3
S4
COM
24V
S1
S2
S3
S4
COM
24V
Y
COM
M
PE
CN9
AO
GND
ROB
ROA
ROC
Y
COM
CN9
AO
GND
ROB
ROA
ROC
PE
r
s
t
PE
(+)
(-)
(+)
(-)
(-)
(+)
PE
Power supply
Input filter
Input
reactor
VFD
Regenerative
reactor
It is recommended
to use fuse.
Regenerative
reactor
It is recommended
to use fuse.
RBU
RBU
Figure 4-8 Parallel connection 2 of RBU100H
Note:
RBU100H 380V 22kW
–45kW has internal output reactor. RBU100H 380V 55kW–250kW/660V
55kW
–400kW has standard output reactor.
Each RBU100H has 1 standard input reactor. Select the input reactor according to the rated
parameters of the VFD.
The input filter is optional. Select the input filter according to the rated parameters of the VFD.
The fuse is optional. Configure the fuse at 1.5 times of the rated current of the RBU.
Derate 90% of the RBU100H in parallel connection.