iMars BD3KTL-PS Energy Storage Inverter Display panel
37
Control item
LCD display
Instruction
On/Off
control
O n / O f f C t r l
O N
O F F
Control the “On/Off” through the panel.
Press “
” and “
” in the control
interface to select the operation. Press
“ENT” to ensure the operation and press
“ESC” to return.
Restart
R e s t a r t
P r e s s E N T t o e x e c u t e .
P r e s s E S C t o c a n c e l .
Restart the inverter through the panel.
And save the all settings and operation
record.
Press “ENT” to ensure restarting and the
inverter will begin to self-inspect or press
“ESC” to return.
Record
clear
C l e a r a l l R e c o r d : S u r e
?
P r e s s E N T t o e x e c u t e .
P r e s s E S C t o c a n c e l .
Press “ENT” to ensure clear all records
or press “ESC” to return.
“Record clear” is to clear all statistic
records through the panel.
Restore to
factory
R e s t o r e t o F a c t o r y
P r e s s E N T t o e x e c u t e .
P r e s s E S C t o c a n c e l .
“Restore to factory” is to clear all setting
parameters and history operation
records through the panel, restore to the
factory setting. Press “ENT” to ensure
clear or press “ESC” to return.
6.3 Grid standard Choice
After power on the inverter by battery input for the first time, if grid frequency was 60Hz, the grid
standard is changed into GNL_60Hz with related protection parameters. Otherwise, it is AS4777
with the related protection parameters at default.
The user can change Grid-connected standard through the following ways:
LCD Screen
:
MENU→Main Menu: Setup→Setup Menu: grid standard→grid standard:
M a i n M e n u
M o n i t P a r a m
S t a t i s t i c s
S e t u p
S y s t e m I n f o
F a u l t I n f o