Goodrive300-01A series VFD for air compressor
Commissioning instruction
-26-
Function code
Parameter setting
Description
2: V/F control
Select the mode according to the motor type.
P00.01
2
2: Communication
P00.06
7
Set via PID control
P01.15
35.00
Stop frequency: 35Hz
P03.27
1
Display as per the set value
P09.00
10
Pressure setting of dedicated function of air
compressor
P09.02
8
Pressure feedback of dedicated function of air
compressor
P11.15
0
Speed deviation protection is disabled
P05.01
6
Coast to stop
P05.10
3
Reversal of S1 and S2 terminal polarity
P05.02
46
External fault (motor overtemperature)
P06.02
29
Cooling fan control of main motor
P06.03
28
Solenoid valve control output
P06.04
27
Fan start/stop control
P05.32
2.04
Lower limit value of P1 corresponds to voltage
2.04V
Step 3 Click
Next
to enter
Parameters Configuration
or click
Back
to return to system configuration.
On the system configuration interface, click
System Para Config
. S1 functions as emergency-stop
switch, select
NO
or
NC
based on the polarity of the emergency-stop switch, as shown in Figure 4-8.
When S2 functions as motor overtemperature, select
NC
based on the polarity.
Figure 4-8 System parameter configuration interface