Goodrive300-01A series VFD for air compressor
Function code description
-69-
Function
code
Name
Description
Default Modify
P18.12
No-load running
frequency
P01.15
–P18.11 (lower-limit frequency of
load-carrying running)
The output working frequency allowed during
no-load of air compressor.
38.00 Hz
○
P18.13
No-load delay
When sleep function is valid, after unloading,
the VFD runs at no-load frequency in the time
set by P18.13, and then enters sleep state.
When air consumption quantity is small, users
can enable sleep function; if sleep function is
valid, it is necessary to lower down P18.13 to
make the device enter sleep state quicker.
Setting range: 0
–3600s
300s
○
P18.14
Stopping delay
After the stopping command becomes valid,
the VFD will first run at no-load frequency in
the time set by P18.14, and then stops.
Setting range: 0
–3600s
0s
○
P18.15
Loading delay
Loading operation is available only after the
motor runs at no-load frequency in the time
set by P18.15.
Setting range: 0
–3600s
10s
○
P18.16
Restart delay
After the system stops, it is necessary to wait
until the time set by P18.16 elapsed before
restart.
Setting range: 0
–3600s
30s
○
P18.17
Pre-alarm pressure
When current discharge pressure is higher
than P18.17, the system indicates pressure
pre-alarm by setting BIT8 of P19.13 to 1.
When current discharge pressure is higher
than P18.18, the system indicates pressure
alarm by setting BIT10 of P19.13 to 1, and
emergency-stop will be applied.
Setting range: 0.00
–P18.04
0.90Mpa
○
P18.18
Alarm pressure
1.00Mpa
○
P18.19 Pre-alarm temperature When machine head temperature is higher
than
P18.19,
the
system
indicates
temperature pre-alarm by setting BIT9 of
P19.13 to 1.
When the machine head temperature is
higher than P18.20, the system indicates
temperature alarm by setting BIT11 of P19.13
105°C
○
P18.20
Alarm temperature
110°C
○
P18.21
Low-temperature
protection threshold
-10°C
○
Summary of Contents for Goodrive300-01A Series
Page 1: ......
Page 175: ...6 6 0 0 1 0 0 5 5 3...