Example 3 -How to connect 2000VA model to PV panels with the following
parameters?
• Pmax
:
250W
• Vmp
:
30.96V
• Voc
:
36.6V
• lmp
:
8.07A
• l
sc
:
8.75A
(1) Max. charging current is 50A,
50A/8.07A = 6.19=>max. Number of PV panel in parallel is 6.
(2) Operating Voltage Range is 32~36V,
One PV panel Vmp 30.96V is between 32~36V => max. Number of PV panel in
parallel is 1.
(3) Taking (1) ~ (2) into consideration, the optimized configuration is 1 PV panels in
series as a string, and 6 strings in parallel (as shown below).
(4) Check again the Voc and Isc of PV string,
Voc of string is 1x36.6V =36.6V < 55V (Max. PV Input Voltage) =>OK
Isc of string is 6x8.75A = 52.5A < 65A (Max. PV Input Current=>OK