APPENDIXA
How to Select and Configure PV Panels
The following parameters can be found in each PV panel's specification:
• Pmax
:
Max output power (W)
• Vm
p
:
Max power voltage (V)
• Voc
:
open-circuit voltage (V)
• Imp
:
Max power current (A)
• l
sc
:
short-circuit current (A)
PV panels can be connected in series or parallel in order to obtain the desired output
voltage and current which meets the inverter's allowed range.
When connecting PV panels in series, the max voltage and current of the
string is
When connecting the above PV string in parallel, the max voltage and current of the
total string is
In either case, the total output power is Ptotal= Ppanel X Number of PV panel
The guideline to select and configure PV string is
• Itota
l shall be equal or slightly larger than the max. capacity of solar battery
charger (50A for 1000VA/2000VA model and 60A for 1200VA/2200VA).
Surplus capacity of PV string does not help the solar charger's capacity and only
result in higher installation cost.
Model
PV panels invested (ltotal)
Max. PV module to support
load
1000VA
50A
500W
1200VA
60A
600W
2000VA
50A
1000W
2200VA
60A
1200W