33
INSTALLATION AND ASSEMBLY
33
iV-Office ventilation device | Installation instructions
Plug-in connector
on the fan cable
Plug-in connector (cable coming from controller)
Start direction extract air
Start direction supply air
Terminal
block
Colour
Terminal
block
Meaning
Colour Terminal
block
Meaning
Colour
CW
Blue
DIR1 (III)
Signal direction 1 White
DIR2 (V)
Signal direction 2
Brown
VIN+
Red
VOUT+ (IV) Operating voltage Green VOUT+ (IV) Operating voltage Green
CCW
Black
DIR2 (V)
Signal direction 2 Brown DIR1 (III)
Signal direction 1
White
The reversible fan is connected to the controller.
4.9 Check function and complete fan installation
►
Set unidirectional ventilation operating mode (DL - through ventilation) on the connected
controller (see the controller's installation and operating instructions).
►
Make sure that all reversible fans rotate in the direction appropriate to their connections.
Start direction extract air mode:
Start direction supply air mode:
Direction of fan clockwise Direction of fan counter clockwise
inVENTron is connected and installed.