Combo Output Module
Product Manual
©2017 INTERRA
61
PM131126001A
5.5.2.1.
Parameters
CONFIGURATION
PARAMETER
DESCRIPTION
VALUES
Fan Coil Function
This parameter determines the function of the fan
coil.
Change Over Object: Selecting this option a new
object is added with which it is possible to change
the operating mode of the fancoil (heating or
cooling).
Command Value: The operating mode of the
fancoil is determined by the command value. The
fancoil works taking into account the last value
received via “Command Value for Heating” or
“Command Value for Cooling” objects.
Change
Over
Object
Command Value
Heating/Cooling Pol. (Normal:
Cooling=0)
1
This parameter determines the value for
activating the two operating mode.
Normal: Cooling=0 / Heating=1.
Inverted: Cooling=1 / Heating=0.
Normal
Inverted
Fan Control Behaviour
This parameter is used to set how the fan coil fan
speed is controlled.
Only One Fan Output at the Same Time: Each fan
speed is controlled individually with a unique
Only
One
Fan
Output
at
the
Same Time