![Interra ITR504 Product Manual Download Page 13](http://html1.mh-extra.com/html/interra/itr504/itr504_product-manual_2080314013.webp)
Combo Output Module
Product Manual
©2017 INTERRA
13
PM131126001A
PARAMETER
DESCRIPTION
VALUES
2 Inputs
3 Inputs
4 Inputs
Output Behaviour
This parameter defines the behaviour of the logic
output.
Normal: The real status of the output is shown via
the corresponding object.
Inverted: The inverted status of the output is
shown via the corresponding object.
Normal
Inverted
Switch On Delay x100ms
The output takes the value on after a delay
configured in this parameter.
0
(0...255)
Switch Off Delay x100ms
The output takes the value off after a delay
configured in this parameter.
0
(0...255)
Cyclic Sending of Feedback
This parameter determines the sending period of
the logic
output value. “Disabled” option means
that the feedback telegram is sent only after
output or input changes, depending on the
previous configuration.
Disabled
5s, 10s, 30s, 1min,
5min,
10min,
20min,
30min,
40min, 50min, 1h.
2h, 3h, 4h, 5h, 6h,
12h, 24h.
3.2.
OBJECTS
The following object can be used through the logic gate function:
OBJ NAME
FUNCTION
TYPE
FLAG
Logic X (1,2,3 or 4)
Input X (1,2,3 or 4)
1 bit
CRWU
Via this object it is possible to set the value of the logic inputs.
Logic X (1,2,3 or 4)
Output
1 bit
CRT
Via this object the current value of the logic output is shown.