Combo Output Module
Product Manual
©2017 INTERRA
28
PM131126001A
OBJ NAME
FUNCTION
TYPE
FLAG
OutputX
Status
1 bit
CRWT
This object is only visible when the
“Feedback Telegram” function is enabled (Normal or Inverted). Via the
group address linked, it indicates the current status of a related output.
OutputX
Scene
1 byte
CRWU
This object is used to recall or store the different scenes previously configured.
OutputX
On/Off
1 bit
CRWU
Via the group address linked, it is possible to switch on and off the lighting channels. Using this object, the
delays configured do not take any effect.
OutputX
Timer
1 bit
CRWTU
This object is used to control the lighting with the delays previously configured.
OutputX
Hours Counter
4 byte
CRWTU
This object is only visible when the “Working Hours Counter” function is enabled. The number of hours that
the lighting channel remains On or Off is shown via this object
. Otherwise, when the “Count Direction”
parameter is configured as “Decrement”, the starting value for the countdown is sent via this object too.
OutputX
Reset Counter
1 bit
CRWTU
This object is only visible when the “Working Hours Counter” function is enabled. Via this object it is possible
to reset the number of hours in the counter.
OutputX
Counter
Set
Point
Reached
1 bit
CRWTU
This object is only visible when the “Working Hours Counter” function is enabled. It takes the value 1 when
the
hours counter takes the value configured in “Set Point for Alert” parameter.
OutputX
Logic Input
1 bit
CRWTU
This object is only visible when the “Logic Function” is enabled. Vis this object the value for the logic input
is set.
OutputX
Flashing
1 bit
CRWU
This object is only visible when the “Flashing” function is enabled.
When this object takes the value 1, the
output is switched on and off periodically. The flashing interval is previously configured.
OutputX
Locking
1 bit
CRWU
This object is only visible when the locking function is enabled. Via the group address linked, it is possible
to activate the locking function and to lock the current output through the value configured previously.