Combo Output Module
Product Manual
©2017 INTERRA
59
PM131126001A
OutputX
Airing Level
1 byte
CRWTU
Via this object the value for airing is set. It is possible to define a fan speed level such as 1, 2 or 3. When
the fan coil is switched off, the fan can be activated with the value configured through this object
OutputX
Constant Fan Level (1-
Byte)
1 byte
CRWTU
Via this object, a constant level for the fan speed such as 1, 2 or 3 can be defined. When a value is sent via
this object, the fan remains that speed regardless of the real operating percentage.
OutputX
Constant Fan Level (1-Bit)
1 bit
CRWTU
Via this object, a constant level for the fan speed can be defined through the sending of consecutive values.
When this object takes the value 1 consecutively, the fan speed is increased. Otherwise, taking the value 0,
the fan speed is decreased.
Note: The first value sent make the fan remain the current fan speed and then the fan speed is increased
or decreased depending of the new values sent.
OutputX
Man./Constant
Fan
Feedback
1 bit
CRWTU
Via the group address linked, it indicates whether the system is operating automatically or, conversely, it
has been forced. The value Off means that there is not forced.