No Reaction/Last State: There is no action on the outputs.
UP: The shutter goes up.
DOWN: The shutter goes down.
Page 1: ...2017 INTERRA ITR504 ITR508 ITR512 ITR516 ITR520 ITR524 4 8 12 16 20 or 24 Channels Combo Output Modules Product Manual...
Page 2: ...disclaims all liability arising from this information and its use Use of Interra devices in life support and or safety applications is entirely at the buyer s risk and the buyer agrees to defend inde...
Page 3: ...hesitate to contact us E mail iletisim interra com tr Tel 90 216 326 26 40 Fax 90 216 324 25 03 Most Current Product Manual To obtain the most up to date version of this product manual please visit o...
Page 4: ...ram Name 4 8 12 16 20 or 24 Combo Output Module Product family Combo Output Module Product name 4 8 12 16 20 or 24 Combo Output Module Media Type Twisted Pair Order number ITR504 16A ITR508 16A ITR512...
Page 5: ...100A inrush Mode of commissioning S Mode Type of protection IP 20 Temperature Range Operation 10 C 70 C Storage 25 C 100 C Maximum air humidity 90 RH Flammability Non flammable product Mounting DIN R...
Page 6: ...HEATING 29 5 2 1 Parameters 31 5 2 2 Objects 35 5 3 SHUTTER BLIND 36 5 3 1 Parameters 40 5 3 2 Objects 46 5 4 SHUTTER BLIND 24V 47 5 5 FAN COILS 48 5 5 1 FAN COIL 2 PIPES 51 5 5 1 1 Parameters 52 5 5...
Page 7: ...eration 49 Fig17 Scene Example 74 Fig18 Shutter Movement Duration 76 Fig19 Shutter Blind Movement Duration 76 Fig2 Staircase Function 18 Fig20 Slat Steps 77 Fig21 Connection Diagram Example Configurat...
Page 8: ...ommunication of the devices via the KNX bus enables information exchanges with KNX sensors and the integration with a building management system The combo has been developed for providing the whole co...
Page 9: ...ITR524 8 X Note The bold values in the tables are the factory settings default values Type and number of the available objects depend on the settings with ETS Visible objects might vary according to...
Page 10: ...this option is enabled See the Appendix A Manual Control 2 1 PARAMETERS PARAMETER DESCRIPTION VALUES Module Alive Beacon This parameter allows sending the value true periodically while the module is r...
Page 11: ...put is shown inversely Through the parameter Send Feedback On the type of feedback can be defined The combo actuator allows sending the result of logic gates when the logic output is changed or conver...
Page 12: ...ermines the logic gate type The output will be true or false depending on the result of this logic Disabled This option is disabled The logic operations AND OR and XOR are possible for this function A...
Page 13: ...akes the value off after a delay configured in this parameter 0 0 255 Cyclic Sending of Feedback This parameter determines the sending period of the logic output value Disabled option means that the f...
Page 14: ...ifferent data values 4 1 PARAMETERS PARAMETER DESCRIPTION VALUES Converter Gate Count This parameter determines the number of converter gates to use No Converter Gate 1 Converter Gate 2 Converter Gate...
Page 15: ...old value for the input when it is configured as 2 Byte Threshold 0 0 65535 Output Type This parameter determines the type of data for the logic output 1 Bit 2 Bits 1 Byte 2 Byte Output Value This par...
Page 16: ...Combo Output Module Product Manual 2017 INTERRA 16 PM131126001A Via this object the current output of the converter is shown...
Page 17: ...ng on the light it will remain ON for a configurable time TSF After this time the output switches off automatically Each time an ON telegram is received while the lights are ON the delay time is resta...
Page 18: ...available for ITR520 and ITR524 FLASHING Via the Flashing communication object the output starts to flash as soon as the value ON is received The period TFI is previously configured in the Flashing I...
Page 19: ...e values parameterized for the output concerned will be overwritten into the actuator It means that any change made by the user will be deleted Therefore it is important before any maintenance to know...
Page 20: ...ailure a delay for the status feedback transmission at startup can be parameterized When this option is used the status of the output after a bus voltage failure is sent once the time delay configured...
Page 21: ...VALUES Contact Type This parameter determines the type of contact output Normally Open The relay works as normally open contact Normally Close The relay works as normally close contact Normally Open...
Page 22: ...ay Hours 0 23 3 Hours of On Delay 0 0 23 On Delay Minutes 0 59 3 Minutes of On Delay 0 0 59 On Delay Seconds 0 59 3 Seconds of On Delay 30 0 59 Off Delay Retriggerable1 This parameter allows the stair...
Page 23: ...ert value for hours counter 1000 1 65535 Periodic Sending of Working Duration4 This parameter determines the sending period of the hours counter current value Disabled option means that the value of t...
Page 24: ...min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h Feedback Periodical Sending6 This parameter determines the sending period of the output current value Disabled option means that the feedbac...
Page 25: ...Combo Output Module Product Manual 2017 INTERRA 25 PM131126001A...
Page 26: ...er is used to assign the number of the scene 1 1 64 Scene 1 16 State This parameter determines the status of the output for the current scene OFF ON Scene 1 16 Storage Function This parameter is used...
Page 27: ...to 0 ON The output is forced to 1 No Reaction Last State OFF ON Logic Function This parameter provides a logic object which is logically linked with the ON OFF object when this option is enabled The o...
Page 28: ...ameter is configured as Decrement the starting value for the countdown is sent via this object too OutputX Reset Counter 1 bit CRWTU This object is only visible when the Working Hours Counter function...
Page 29: ...r than the upper limit The hysteresis value is the result of the subtraction between Upper Limit and Lower Limit In the next example the Upper Limit 25 and the Lower Limit 15 It means that the hystere...
Page 30: ...the period configured Additionally to reduce the bus traffic after any failure a delay for the status feedback transmission at startup can be parameterized When this option is used the status of the...
Page 31: ...sed No Periodically Open Valve 5 min every 24h Summer Winter Mode Switch Over This parameter provides an object which can be used as summer winter switch No Yes Summer Winter Pol Normal Sum 0 Win 1 1...
Page 32: ...he output to go back to off It must be a value smaller than the upper limit 10 0 100 Upper Limit 2 This value set the value of the valve opening It must be a value greater than 0 10 0 100 Forced Posit...
Page 33: ...1h 2h 3h 4h 5h 6h 12h 24h Feedback Periodical Sending4 This parameter determines the sending period of the output current value Disabled option means that the feedback telegram is sent only after outp...
Page 34: ...odule Product Manual 2017 INTERRA 34 PM131126001A 3These parameters are only visible when the parameter Forced Position is enabled 4These parameters are only visible when the parameter Feedback Telegr...
Page 35: ...s on or off OutputX Manipulated Value 1 byte CRWU This object is only visible when the Type of Manipulated Variable is set to Continuous 1 Byte Via this object the valve is controlled with percentages...
Page 36: ...ilable In contrast to the shutter function when the blind is at rest the telegrams received via the object Slat Angle Stop allow the positioning of the slats Slat Angle Stop When the positioning of th...
Page 37: ...0 180 This parameter determines the number of steps required to move the slats from the 0 position to the 180 position The time of these steps is configured through the parameter Duration of Short Mov...
Page 38: ...via the object scene must be 23 On the other hand the value 152 128 23 must be sent for storage the scene number 24 The recall of each scene can be delayed whether a time delay has been defined previo...
Page 39: ...Combo Output Module Product Manual 2017 INTERRA 39 PM131126001A No Reaction Last State There is no action on the outputs UP The shutter goes up DOWN The shutter goes down...
Page 40: ...n Movement Duration sec This parameter set the time of the down shutter movement duration 120 0 255 Duration of Short Movement x50ms This parameter set the time for the short movements when the shutte...
Page 41: ...parameter determines the behaviour of the shutter at the beginning of locking No Reaction There is no reaction the shutter remains the last state Up The shutter goes up Down The shutter goes down No R...
Page 42: ...ns that the feedback telegram is sent only after output changes not periodically Disabled 5s 10s 30s 1min 5min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h 1This parameter is only visible w...
Page 43: ...osition Value 0 100 This parameter set the position of the shutter for a particular scene 0 0 100 Scene 1 16 Slat Angle Value 0 180 This parameter set the slat angle value for a particular scene 0 0 1...
Page 44: ...hutter when a wind alarm is ended No Reaction The shutter remains the last state Up The shutter is upped Down The shutter is lowered Value It is possible to define a position value in No Reaction Up D...
Page 45: ...hen a frost alarm occurs No Reaction The shutter remains the last state Up The shutter is upped Down The shutter is lowered Value It is possible to define a position value in No Reaction Up Down Value...
Page 46: ...OutputX Moving Status 1 bit CRWTU This object takes the value 1 while the shutter is moving up or down Otherwise the value of the object is 0 OutputX Slat Position 1 byte CRWU This object is only visi...
Page 47: ...47 PM131126001A 5 4 SHUTTER BLIND 24V The application description for Shutter Blind 24v is the same as Shutter Blind The unique difference between these two options is the number of outputs needed 2...
Page 48: ...is increased in steps Depending on the command value 1 byte whose value comes from the thermostat or room master the combo determines the corresponding fan speeds via configurable threshold values He...
Page 49: ...g functions is used and return to the automatic mode is required it is necessary to use the Return to Automatic Mode object When this object takes the value 1 every forced are disabled and the system...
Page 50: ...action of the output during bus voltage failure can be configured too The combo actuator allows two different behaviours for bus voltage failure No Reaction There is no reaction the outputs remain the...
Page 51: ...hich is supplied centrally Heating Cooling In this system only one water circuit is available for heating and cooling Depending on the central system warm or cold water is supplied to the pipe system...
Page 52: ...nly Cooling Heating Cooling Fan Control Behaviour This parameter is used to set how the fan coil fan speed is controlled Only One Fan Output at the Same Time Each fan speed is controlled individually...
Page 53: ...rameter set the low threshold value for the fan 3 70 1 100 Hysteresis for Fan Limit 0 20 This parameter determines the hysteresis for fan limits This value is proportional to the limits configured pre...
Page 54: ...ion of the function Switch Off All Outputs The outputs are switched off Operation with Fan Level The fan speed is set to a value configured in the next parameter No Reaction Switch Off All Outputs Ope...
Page 55: ...Product Manual 2017 INTERRA 55 PM131126001A PARAMETER DESCRIPTION VALUES take the values according to the last command received Note If during the disabling the operating mode is changed it is always...
Page 56: ...ched off No Reaction Switch Off All Outputs Feedback Telegram This parameter is used to set weather the status of the fan coil and the fan speed are shown Disabled There is no information about the st...
Page 57: ...ut changes not periodically Disabled 5s 10s 30s 1min 5min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h Feedback Type This parameter defines the type of feedback for the fan speed Fan level...
Page 58: ...n the Feedback Type parameter is set to Fan Levels Individually Via the group address linked it indicates the current status of the fan speed 2 OutputX Feedback for Fan Level 3 1 bit CRWTU This object...
Page 59: ...peed regardless of the real operating percentage OutputX Constant Fan Level 1 Bit 1 bit CRWTU Via this object a constant level for the fan speed can be defined through the sending of consecutive value...
Page 60: ...ge Over Object a new communication object is added Heating Cooling Change Over which defines the operating mode of the fan coil With the normal configuration when this object takes the value 0 the fan...
Page 61: ...determined by the command value The fancoil works taking into account the last value received via Command Value for Heating or Command Value for Cooling objects Change Over Object Command Value Heatin...
Page 62: ...rameter set the low threshold value for the fan 1 5 1 100 Fan 2 Lower Limit 1 100 This parameter set the low threshold value for the fan 2 30 1 100 Fan 3 Lower Limit 1 100 This parameter set the low t...
Page 63: ...ion of the function Switch Off All Outputs The outputs are switched off Operation with Fan Level The fan speed is set to a value configured in the next parameter No Reaction Switch Off All Outputs Ope...
Page 64: ...Product Manual 2017 INTERRA 64 PM131126001A PARAMETER DESCRIPTION VALUES take the values according to the last command received Note If during the disabling the operating mode is changed it is always...
Page 65: ...ched off No Reaction Switch Off All Outputs Feedback Telegram This parameter is used to set weather the status of the fan coil and the fan speed are shown Disabled There is no information about the st...
Page 66: ...ut changes not periodically Disabled 5s 10s 30s 1min 5min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h Feedback Type This parameter defines the type of feedback for the fan speed Fan level...
Page 67: ...ype parameter is set to Fan Levels Individually Via the group address linked it indicates the current status of the fan speed 2 OutputX Feedback for Fan Level 3 1 bit CRWTU This object is only visible...
Page 68: ...tX Constant Fan Level 1 Bit 1 bit CRWTU Via this object the fan speed can be forced to a certain level through the sending of consecutive values When this object takes the value 1 consecutively the fa...
Page 69: ...ented via the status led and is transmitted to the bus via the status object SHUTTER BLIND Shutter and blinds can be lowered or raised with a long push button action while a short push button action e...
Page 70: ...0 0 1 1 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Function Input 1 Input 2 Input 3 Input 4 Output OR 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0...
Page 71: ...odule Product Manual 2017 INTERRA 71 PM131126001A XOR 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0 1 0 0 1 1...
Page 72: ...The activation of the scene involves the following actions The shutter is positioned to 50 and 90 25 seconds after scene recall the light 1 is switched off 30 seconds after scene recall the light 2 is...
Page 73: ...KNX devices in a scene The value of the scene can be modified through the storage option In the above example the light 2 is switched on recalling the scene 24 If it is required that the light 2 is sw...
Page 74: ...e shutter starts to move from that position to the completely opened position On the contrary for measuring the down movement duration the shutter should be positioned to the completely opened positio...
Page 75: ...the 180 position For measuring this number of steps the slats should be positioned to the completely closed position 0 and then start to move the slats step by step and counting them at the same time...
Page 76: ...TR520 4 1 6 7 12 13 18 and 19 20 ITR524 4 1 6 7 12 13 18 and 19 24 Example Out 1 2 3 4 configured as fan coil 2 pipes This allows configuring the output 5 and 6 as shutter blind or lighting and heatin...
Page 77: ...HEATING Out 4 LIGHTING HEATING Out 5 LIGHTING Out 6 LIGHTING HEATING Out 1 HEATING Out 2 LIGHTING HEATING Out 3 HEATING Out 4 LIGHTING HEATING Out 5 HEATING Out 6 LIGHTING HEATING Out 1 HEATING Out 2...
Page 78: ...UTTER BLIND Out 1 2 3 4 SHUTTER BLIND 24V Out 5 LIGHTING Out 6 LIGHTING HEATING Out 1 2 3 4 SHUTTER BLIND 24V Out 5 HEATING Out 6 LIGHTING HEATING Out 1 2 3 4 SHUTTER BLIND 24V Out 5 6 SHUTTER BLIND O...
Page 79: ...HEATING Out 2 LIGHTING Out 8 LIGHTING Out 3 HEATING Out 9 HEATING Out 4 HEATING Out 10 HEATING Out 5 LIGHTING Out 11 LIGHTING Out 6 HEATING Out 12 LIGHTING Fig21 Connection Diagram Example Configurat...
Page 80: ...Example Configuration 2 The combo module only allows configuring the first inputs as fancoil 2 or 4 pipes In the example above the inputs C1 C4 are used for the connection of a 2 pipes fancoil and th...
Page 81: ...onnection Diagram Example Configuration 3 Every output of the combo module can be configured as shutter blind provided that 2 consecutive outputs are available However for the shutter blind 24V config...
Page 82: ...your favourite Internet browser the web site contains the following information Overview of Interra Technology company and values Information about our products and projects Product Support Data shee...