TruPortal IP-based Single Door Controller Quick Reference 

9

Specifications

Regulatory Information

Contact Information

www.interlogix.com

Customer support: 

www.interlogix.com/support

© 30OCT13 United Technologies Corporation

Interlogix is part of UTC Climate, Controls & Security, a unit of 
United Technologies Corporation.  All rights reserved.

Document number: 460939301C - October 2013

Dimensions (Height × 
Width × Depth)

10.15 in. x 9.15 in. x 3.04 in.
(258 mm x 232 mm x 77 mm)

Operating 
environment 

temperature

[1]

1. +32° to +120° F (0° to +49° C)

+35 to +122° F (+2 to +50° C)

Humidity range

[2]

2. Up to 85% non-condensing

5 to 95% non-condensing

Thermal air cooling

At least 6 in. (15.2 cm) of clearance is required on all 

four sides of the enclosure.

Power input 
requirements

IEEE802.3af 16 watt Class 0 Mode A and B PoE/
PSE) on Standard Category 5 (CAT 5) Ethernet cable 

Note:

 By Ethernet standards, the maximum cable 

length is limited to 328 ft. (100 m) between the PoE 
source and the IPSDC.
-or-

Auxiliary 24 VDC 1 A local supply (24 watts).

IPSDC to reader 
cabling

Reader voltage: 12 VDC

Note: 

If the cable distance is greater than 500 feet 

(152.4 m), but less than or equal to 2000 feet 
(609.6m) and/or the current per reader is greater than 
150 mA, use 20 AWG shielded cable.
If the cable distance is less than 500 feet (152.4 m), 
use 22 AWG shielded cable.

Recommended: 

Use 20 AWG shielded cable to wire 

reader, DOs, and DIs. Use plenum-rated cable for 
applications where cable will run above a false (i.e., 
suspended) ceiling in the air circulation space.

Recommended:

 Alpha Xtra Guard1 foil shield cable, 

non-plenum-rated, or Belden-series security and 
alarm cable (commercial applications shielded), 
plenum-rated.

Readers

Maximum number of readers supported: 2
Reader technology supported: Wiegand
Output devices maximum ratings: Door DO (Reader 
LED) = 20.mA @ 12 VDC maximum; Door strike 
(DO) relay = 2 A @ 28 VDC or 30 VAC maximum

Strikes

Maximum current: 390 mA per strike output. See 
Table 2 on page 2 for recommended strike models 
and associated power requirements.

Network 
requirements

Although IPSDCs are equipped with a fallback mode, 

they should be placed on a network with an adequate 
reliability rate. (A network reliability rate of 99.98 
percent is typical for mission-critical operations.) 

If a typical Mean Time To Repair (MTTR) goal is one 
hour, then using the 99.98% reliability rate equates to 
a mean network reliability, or Mean Time Between 
Failure (MTBF), goal of approximately 5,000 hours (or 
1hr/.0002). In other words, the network that the 
IPSDC is being placed on (from the door controller to 
the System Controller), should not fail more often than 
once every 5,000 hours (or approximately 208 days) 
on average. 

UL evaluation for UL-Listed Installations:

Manufacturer Interlogix 

Headquarters and Regulatory responsibility: 

Interlogix
3211 Progress Dr.
Lincolnton, NC 28092 USA 

EU authorized manufacturing representative: 

UTC Climate, Controls & Security B.V., 
Kelvinstraat 7, 6003 DH Weert, 
The Netherlands

Year of 
manufacture

The first two digits of the product serial number (located 
on the product identification label) are the year of 
manufacture.

North American 
standards

UL 294

FCC 
compliance

This device complies with part 15 of the FCC Rules. 
Operation is subject to the following two conditions: (1) 
This device may not cause harmful interference, and (2) 
this device must accept any interference received, 
including interference that may cause undesired 
operation.

Environmental 
Class

UL: Indoor dry

Certification  

European Union 
directives

We declare under our sole responsibility that this product 
is in conformity with Directive 1999/5/EC (R&TTE), 2004/
108/EC (EMC), 2006/95/EC (LVD), and 93/68/EEC 
(Marking) based on test results using harmonized 
standards in accordance with the Directives mentioned.

Summary of Contents for TruPortal TP-ADD-1DIP

Page 1: ...TruPortal IPSDC board only Capable of controlling one door No enclosure or readers included Installation Procedure To install the IPSDC perform the procedures described in the following sections in t...

Page 2: ...stom Wiegand Card Format 1 1 Use the System Administration Card Formats page in the TruPortal User Interface to configure Wiegand card formats Set SW1 1 to OFF and set SW1 2 thru SW1 4 to ON SW2 Set a...

Page 3: ...quirements Wattage Calculator worksheet included on the product disc for strike type and size 6 Strike voltage selection Jumper pins 1 and 2 for 24 VDC strikes jumper pins 2 and 3 for 12 VDC strikes 7...

Page 4: ...the cable through ferrite provided as shown in Figure 5 Note Ferrite must be installed inside of the enclosure Figure 3 Using Shielded Cable and Drain Wire Figure 4 Wiring Earth Ground Figure 5 Instal...

Page 5: ...ake sure that the PC is not blocked from connecting to IP address 192 168 6 6 If the workstation normally connects to the Internet via a proxy the proxy settings in the browser may need to be adjusted...

Page 6: ...nclosure tamper W5 4 Strike Voltage Select W2 14 Boot Mode switch SW4 5 Custom Wiegand Card Format DIP switch SW1 15 Hardware Reset switch SW5 6 Reader Out Egress J3 16 Shutdown Request switch SW6 7 D...

Page 7: ...REX 2 17 1K EOL resistors typical 3 Connector J3 18 Reader 2 egress 19 12 VDC Red 20 Ground 0V Black 21 Reader Data 0 Green 22 Reader Data 1 White 23 Door DO green LED Orange 24 26 Not used 27 Drain w...

Page 8: ...uest Normally OFF Flashes and then ON 10 D33 StrikeActivated ON during strike activation 11 D24 FACP not supported by IPSDC ON contact open 12 D25 Door Contact ON contact closed OFF contact open Flash...

Page 9: ...ratings Door DO Reader LED 20 mA 12 VDC maximum Door strike DO relay 2A 28 VDC or 30 VAC maximum Strikes Maximum current 390 mA per strike output See Table 2 on page 2 for recommended strike models a...