EN: Installation Sheet 

Mounting the unit  

The board has a standard Aritech ‘B’ size footprint, mountable 
in an existing Aritech metalwork. 

Connections J2 

• 

+12 V: 12 VDC supply input. 100 mA maximum. 

• 

0 V: Negative supply. 

• 

D+: Positive data connection of the RS485 databus. 

• 

D−: Negative data connection of the RS485 databus. 

Units can be up to 1.5 km from the 4-door DGP or control 
panel, depending on the type of cable used. Recommended 
cable is WCAT 52/54; 2-pair twisted, shielded, data cable. 

Connections J1 

• 

TX: RS232 data transmit. 

• 

RX: RS232 data receive. 

• 

CTS: Clear to send. 

• 

RTS: Request to send. 

• 

GND: Isolated RS232 ground. 

LEDs 

• 

TX LED: LED flashes to indicate data is being received in 
as RS232

 

and transmitted out as RS485. 

• 

RX LED: LED flashes to indicate data is being received in 
as RS485 and transmitted out as RS232. 

Extended distances between Titan and 
ATS1801 

ATS1741 (RS485 to RS232 interface) to PC 

ATS1741 (RS232) 

PC (RS232) 

Pin Names 

Pin Names 

DB25 

DB9 

TX 

RX 

RX 

TX 

*CTS 

*Not connected 

6, 8, 20 

1, 4, 6 

*RTS 

*Not connected 

 

 

GND 

GND 

*Link RTS-CTS 

*Link RTS-CTS 

4-5 

7-8 

ATS1741 (RS485 to RS232 interface) - ATS1741 (RS485 to RS232 
interface) 

ATS1741 
(RS485) 

ATS1741 
(RS485) 

Remarks 

+12 V 
0 V 

+12 V 
0V 

Connect to a 12 VDC power supply from 
one control panel 

D+ 

D+ 

 

D

− 

D− 

 

Caution: 

Do not power the ATS1741 from different power 

supplies unless you disconnect the +12 V wiring between 
those units. Ensure the power supplies are isolated, especially 
the GND. 

ATS1741 (RS485 to RS232 interface) 

– ATS1801 (Computer/Printer 

interface) 

ATS1741 (RS232) 

ATS1801 Port Computer 

TX 

RxD 

RX 

TxD 

CTS* 

*Not connected 

RTS* 

Not connected 

GND 

GND 

*Link RTS-CTS 

*+12 V on CTS 

 

Data bus System Via Modem 

The shield of each length of data cable is only connected to 
earth at one end. 

The connections between ATS1741 and the modem are as 
follows. 

 

 

Summary of Contents for ATS1741 RS232

Page 1: ...s RS485 RX LED LED flashes to indicate data is being received in as RS485 and transmitted out as RS232 Extended distances between Titan and ATS1801 ATS1741 RS485 to RS232 interface to PC ATS1741 RS232...

Page 2: ...g return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info Contact inform...

Page 3: ...y erkl rer hermed at denne enhed er i overensstemmelse med g ldende krav og bestemmelser i direktivet 2014 30 EU og eller 2014 35 EU For yderligere informationer se www utcfireandsecurity com eller ww...

Page 4: ...erend Rechtliche Hinweise Hersteller INVERKEHRBRINGER UTC Fire Security Americas Corporation Inc 3211 Progress Drive Lincolnton NC 28092 USA BEVOLLM CHTIGTER EU REPR SENDANT UTC Fire Security B V Kelv...

Page 5: ...ND 7 5 Enlace RTS CTS Enlace RTS CTS 4 5 7 8 ATS1741 interface entre RS485 y RS232 ATS1741 interface entre RS485 y RS232 ATS1741 RS485 ATS1741 RS232 Comentarios 12 V 0 V 12 V 0V Se debe conectar con u...

Page 6: ...ritechin metallikoteloon J2 liit nn t 12 V 12 VDC n tehonsy tt Enint n 100 mA 0 V Negatiivinen sy tt D RS485 datav yl n positiivinen datayhteys D RS485 datav yl n negatiivinen datayhteys K ytett v st...

Page 7: ...oitteista www utcfireandsecurity com tai www interlogix com 2012 19 EU WEEE direktiivi T ll symbolilla merkittyj tuotteita ei saa h vitt Euroopan Unionin alueella talousj tteen mukana kaupungin j tehu...

Page 8: ...RE SECURITY NE PEUT GARANTIR QU UNE PERSONNE OU ENTIT FAISANT L ACQUISITION DE CEUX CI Y COMPRIS UN REVENDEUR AGR DISPOSE DE LA FORMATION OU DE L EXP RIENCE REQUISE POUR PROC DER CETTE M ME INSTALLATI...

Page 9: ...massima di funzionamento 100 mA Temperatura di esercizio Da 0 a 50 C Umidit relativa 95 senza condensa Certificazione e conformit Costruttore MESSO SUL MERCATO DA UTC Fire Security Americas Corporatio...

Page 10: ...nterface RS485 naar RS232 ATS1741 Interface RS485 naar RS232 ATS1741 RS485 ATS1741 RS485 Opmerkingen 12 V 0 V 12 V 0V Aansluiten op 12 VDC voeding van een controlepaneel D D D D Waarschuwing Sluit de...

Page 11: ...itech kapslinger Tilkoblinger J2 12 V 12 VDC str mforsyningsinngang Maksimalt 100 mA 0 V Negativ str mforsyning D Den positive datatilkoblingen til RS485 databussen D Den negative datatilkoblingen til...

Page 12: ...ionen For riktig gjenvinning returner dette produktet til din lokale leverand r n r du kj per et nytt produkt av tilsvarende type eller lever det ved ett dedikert oppsamlingspunkt For mer informasjon...

Page 13: ...ZOWANI SPRZEDAWCY ORAZ AUTORYZOWANI DEALERZY S PRAWID OWO PRZESZKOLENI LUB DO WIADCZENI TAK BY MOGLI PRAWID OWO ZAMONTOWA PRODUKTY ZABEZPIECZAJ CE Wi cej informacji o zastrze eniach dotycz cych gwaran...

Page 14: ...em 1 Especifica es Tens o de alimenta o 12 V Corrente de opera o 100 mA Temperatura de opera o 0 a 50 C Humidade relativa 95 sem condensa o Informa o reguladora Fabricante COLOCADO NO MERCADO POR UTC...

Page 15: ...jord GND jord 7 5 Bygel RTS CTS Bygel RTS CTS 4 5 7 8 ATS1741 RS485 till RS232 gr nssnittet ATS1741 RS485 till RS232 gr nssnittet ATS1741 RS232 ATS1741 RS232 Anm rkningar 12 V 0 V 12 V 0V Anslut till...

Page 16: ...roduct warning eller skanna QR koden Certifiering UTC Fire Security meddelar harmed att denna product verinst mmer med med till mpliga krav och best mmelser f r Directive 2014 30 EU och eller 2014 35...

Reviews: