ILC LightLEEDer Operation Manual
Version 1C 3/14/17
LightLEEDer UL 924 Emergency Relay Bypass Output Module (RBOM) details:
The RBOM mounts in the same location as a standard Relay Output Module, as shown on lighting controller detail 1.3,
and uses the same mounting screws and ribbon connections to the R40 relays.
normal power must be run to the panel power transformer providing the 24VAC CT connection to the RBOM from
the power distribution board.
note: Do not feed the panel processor or transformer from the emergency power source. Only the load relays con-
trolling emergency lighting are fed from the emergency power source.
The RBOM has an leD status indicator for 24V power to the board, and VIO from the ribbon cable. The same standard
24VAC CT 3-wire power connections are used on both the RBOM and the standard Relay Output Module (ROM).
The installer may use relays on only one side of the enclosure for emergency loads, or the entire panel may be emer-
gency loads, ( see submittal documents for panel configuration).
Two rows of four jumpers are provided for selection of the emergency operation of each relay output on the odd or
even side of the RBOM. These jumpers allow selection of; Force On, Force Off, and no Control for each relay during a
power outage to the panel.
each RBOM has a “TesT” button for triggering the module into the eM state, and a status leD that flashes when the
module is triggered. Auxiliary connectors are provided for an optional external test station momentary closure (J4)
and normal power status led (J5)
see Figure 1
Appendix M
5.0"
3.5"
-
RL
Y 1
+
RL
Y 3
RL
Y 5
RL
Y 7
RL
Y 2
RL
Y 4
RL
Y 6
RL
Y 8
-
+
+
-
+
+
-
-
-
+
+
-
24VAC CT
24VAC CT
+
-
+
+
-
77013540A
97013540
-
+
POWER
J4
J5
LED3
VIO
1
2
2
1
+
ON
NC
OFF
OFF
NC
ON
A
TEST
A
A
R1
R2
R3
R4
R5
R6
R7
R8
RELAY OUTPUTS
RIBBON CABLE CONNECTORS
24VAC CENTER TAP
3-WIRE POWER CONNECTOR
EM - RELAY ACTION JUMPERS
OFF = FORCE OFF
NC = NO CHANGE
ON = FORCE ON *
* DEFAULT SELECTION
RIBBON CABLE CONNECTION
PANEL COMMUNICATION
J4 CONNECTOR FOR
REMOTE TEST BUTTON
24VAC CENTER TAP
3-WIRE POWER CONNECTOR
OUT TO NEXT RBOM
RIBBON CABLE CONNECTION
PANEL COMMUNICATION
OUT TO NEXT RBOM
EM TRIGGER LED
VIO STATUS LED
(5VDC FROM I/O)
POWER STATUS
LED (24V )
EM OPERATION
TEST BUTTON
OPTIONAL REMOTE TESTS STATION
Momentary
KEY SW
RED
LED
J5 CONNECTOR FOR
REMOTE STATUS LED
Figure 1 - Relay Bypass Output Module details