ILC LightLEEDer Operation Manual
Version 1C 3/14/17
N2 Module (panel level)
The lightleeDer Controller(s) can be integrated into a Building Automation system (BAs) that uses the n2 communi-
cations protocol. The host system can then poll the status of the lightMaster Controller inputs and outputs and issue
On/OFF commands to the lightleeDer ’s relay outputs. With the panel module, commands can be sent to the panel
to force relays On and OFF, force relays On and OFF with a timer option (blink, double blink, hID delay, Alarm On,
Alarm OFF, Pulse On, and Pulse OFF), monitor relay status, monitor input status, and enable/disable inputs.
Setup:
1. From the home screen, press
eDIT
(Networked Panels
connect to the Network Controller Node 00 as shown in
Section 3.0)
2. Press
2 times to scroll down
3. Press
OTheR DeVICes
4. Press
ADD-On MODUles
5. Press
ADD-On MODUle 1, 2, 3, or 4
6. Press
or
and select the n2 option
ILC LIGHTLEEDER
TUE 01/21/11
.
09:46:54 PM
.
EDIT
NODE 01
.
TIMERS
CLOCK
PRESETS
OTHER DEVICES
ADD-ON MODULES
DIMMER OUTPUTS
MOTOR OUTPUTS
ADD-ON MODULE 1
ADD-ON MODULE 2
ADD-ON MODULE 3
ADD-ON MODULE 4
ADD-ON MODULE 1
TYPE:N2
EDIT
N2 Module Setup
Press
eDIT, then
twice
Press
OTheR DeVICes
Press
ADD-On MODUles
Press
ADD-On MODUle 1, 2, 3, or 4
Appendix h
Press
or
and select
the n2 option
LightLEEDer N2 Control Module
(Panel level)
97013492
77013492A
ADDRESS
2.0”
3.0”
Ribbon connector to panel
N2 cable
termination
Device addressing
switches
For a LightLEEDer N2 point map go to:
http://ilc-usa.com/product_detail.php?pid=32