ILC LightLEEDer Operation Manual
Version 1C 3/14/17
Programming
3.6.5 Configure Relay Groups
Relays can be grouped together to make it easy to program timers
and inputs. The lightleeDer has the capability of 256 groups that are
network-wide.
1. From the home screen, press
eDIT
(Networked Panels
connect to the Network Controller Node 00 as shown in
Section 3.0)
2. Press
RelAYs
3. Press
gROUP RelAYs
4. Press
or
to select the group desired
5. Press
RelAY
6. Press
or
to select the relay
7. Press
InClUDe to toggle between Yes and nO
8. Press “ hOMe” to exit to the home screen
3.6.6 Map an Input to Control Relays or Groups
Inputs must be programmed to control the relays to the desired ac-
tion. This is accomplished at the panel level for each node.
Note:
Inputs
must be configured using the procedure in section 3.5 prior to mapping
The relay control actions are listed below and the control may vary
depending on the input type selected as shown.
1. From the home screen, press
eDIT
(Networked Panels
connect to the Network Controller Node 00 as shown in
Section 3.0)
2. Press
RelAYs
3. Press
InPUT MAPPIng
For Local Inputs to Relay Control
4. Press
lOCAl/RelAYs
5. Press
or
to select the lightsync input device address
6. Press
InPUT
7. Press
or
to select the lightsync Input
8. Press
RelAY
9. Press
or
to select the relay to be controlled
10. Press
ACTIOn
11. Press
or
to select the action (On (A), OFF (B), On-OFF)
RELAY STATUS
RELAY OPTIONS
GROUP RELAYS
INPUT MAPPING
From the RelAY screen, press
gROUP RelAYs
RELAY GROUPS
GROUP: GROUP:001
RELAY: RLY:01.01
INLUCDE:YES
scroll to the desired group
RELAY GROUPS
GROUP: GROUP:001
RELAY: RLY:01.01
INCLUDE:YES
RELAY GROUPS
GROUP: GROUP:001
RELAY: RLY:01.01
INCLUDE:YES
RELAY STATUS
RELAY OPTIONS
GROUP RELAYS
INPUT MAPPING
From the RelAY screen, press
InPUT MAPPIng
INPUT MAPPING
LOCAL/RELAYS
LOCAL/GROUPS
NETWORK INPUTS
Press
lOCAl/RelAYs
DEVICE IN:01.01.1
INPUT
RELAY RLY:01.01
ACTION NONE
Configure Relay Groups
Map an Input to Control Local Relays
Press
RelAY and scroll to the relay
to include (or remove) in group
Press
InClUDe to add or remove
relay from group
Table 3.11: Relay Action
• ON (SA H-P)
= On only, hID power, step A for 2/4 step switching
• OFF (SB H/L)
= OFF only, hID high-low n.O., step B for 2/4 step
switching
• ON-OFF (H/C)
= On/OFF, hID high-low n.C., step A for 2/4 step
switching
Press
InPUT and scroll to the desired input
Then Press
RelAY and scroll to the desired relay.
Then Press
ACTIOn and scroll to the desired action.
Continued on next page