CHARGER VOLTAGE ADJUSTMENT:
** NO MODIFICATIONS RECOMMENDED
–
ONLY BY TECHNICIANS **
Charger voltage can be adjusted
ADD: for increasing
SUB: for decreasing
Set values with keys:
&
15
INVERTER VOLTAGE ADJUSTMENT:
** NO MODIFICATIONS RECOMMENDED
–
ONLY BY TECHNICIANS **
Inverter output voltage can be adjusted
ADD: for increasing
SUB: for decreasing
Set values with keys:
&
16
VOLTAGE OUTPUT VALUE ON LCD:
This function calibrates output voltage value indicated on LCD.
ADD: for increasing
SUB: for decreasing
Set values with keys:
&
** THIS FUNCTION ONLY WORKS IF UPS IS CONNECTED IN PARALLEL.
17
CHARGER CURRENT ADJUSTMENT:
BOTTOM PARAMETER
Charging current can be selected: 1A/2A/3A/4A
Set value by keys:
&
** NO MODIFICATIONS RECOMMENDED
–
ONLY BY TECHNICIANS **
This is used when additional external batteries are connected to UPS and charger current
needs to be increased to recharge in shorter time.
-
UPS WITH STANDARD BATTERIES: 1A
-
UPS WITH 1 ADDITIONAL EXTERNAL BATTERY PACK: 2A or 3A
-
UPS WITH 2 ADDITIONAL EXTERNAL BATTERY PACKS: 4A
UPPER PARAMETER:
It allows to adjust real charger current. If charger current is selected as 1A but when it
is measured it is 0.7A, real current can be adjusting by 3 in this parameter.