USER MANUAL 

 OPTIMA-T10 6K/10K (UL) 

 

 

www.xmart-ups.com 

VER.190731-GA2UL (ENG)

 

20 

 

5.

 

OPERATION MODES 

 

This is a True Online Double Conversion UPS and it is designed to offer clean, bump-less and highest quality power to your computer 

related equipment protecting also your valuable data. Power delivered by UPS is 100% sine wave as main line. 

According to AC main service, and how UPS has been configured, it may operate in following modes: 

 

ONLINE NORMAL Mode  

When UPS is off by selecting ON push button in front panel UPS enters ONLINE NORMAL mode if AC main service is inside acceptable 

input range. Under this mode UPS Inverter powers outputs and the energy is taken from DC voltage coming from AC/DC converter. Batteries 

are charged by AC Line if required. 

 

BATTERY Mode (Also known Inverter Mode) 

If under ONLINE NORMAL mode UPS detects a problem in AC input Line, it enters in battery mode. Under this mode UPS takes energy 

from batteries to feed inverter that generates power for the output. There are no transfers neither micro-cuts on UPS output as inverter was 

already working. The only difference is that energy is now coming from batteries instead of rectifier output. Transfer time is actually Zero 

(0ms). UPS also can enter in battery mode when it is turned on without an acceptable AC input. 

 

STATIC BYPASS (INTERNAL BYPASS):

  

This mode can be adopted if UPS configuration allows BYPASS mode. This configuration is done by using configuration menus in LCD. 

Factory preset for 6K and 10K models is BYPASS mode allowed. 

 

Under bypass mode, UPS AC output is feed from UPS AC input. This mode can be adopted by operator by pressing OFF button in front 

panel (if BYAPSS mode is enable) or automatically in case a problem is detected by UPS. When UPS is in bypass mode, in case AC input 

is interrupted, output will be interrupted also, and UPS will power off. No battery mode can be adopted from bypass mode. 

 

Bypass mode can be caused by any of below conditions: 

 

1-

 

Bypass mode is adopted, as soon as UPS detects a valid AC input on its terminals. (If bypass mode is not enabling, UPS will 

simply light its LCD. Outputs will keep powered off)  

2-

 

Bypass mode is adopted as soon as a problem is detected in its internal circuitries. 

3-

 

Bypass mode is also activated in case an external overload is detected in UPS output. It happens when equipment connected 

to UPS output requires a power higher than max. power of the UPS: 

 

MAINTENANCE BYPASS:

  

This is the mode adopted when external bypass switch is activated. On this mode output is feed directly from AC input through external 

bypass lines. On Maintenance Bypass mode, UPS can be turned-off for maintenance. 

In OPTIMA-T10 models tower type there is a maintenance bypass switch (named MBS) located on rear panel. This switch is covered by 

a safety plate.  

 

 

Additionally, this UPS can adopt under operator demand other operation modes as described: 

 

FREQUENCY CONVERSION:

 

 

 

 

      

 

 

 

This UPS offers a very sophisticated function named frequency conversion (CF) that allows UPS to generate power output at determined 

frequency value (50Hz or 60Hz) no matter input frequency value. UPs will be able to generate output at 50Hz even input source is at 60Hz 

or generate 60Hz even if connected to 50Hz source. 

This function can be configured and activated by LCD. Revise configuration section of this manual. 

 

ECO:

  

Under this mode, UPS powers outputs from the AC input. This is a kind of supervised BYPASS mode. As soon as AC input is out of 

acceptable input range for ECO mode (as defined on LCD configuration menus), UPS switch UPS from ECO to ONLINE mode or battery 

mode. Online mode is adopted if input range is acceptable for ONLINE mode. Switching from ECO to other mode takes about 4ms to10ms. 

ECO mode must be activated on LCD according to configuration section of this manual. 

 

IMPORTANT NOTES: 

1.- Under CF mode, UPS will disable BYPASS mode. Since UPS has been configured to generate output with frequency value different to 

input frequency, BYPASS mode is disabled to avoid a not acceptable frequency value at output. 

2.- When CF function is activated, maximum power output is de-rated to 60% of maximum nominal capacity. For example, for a 10KVA 

(8KW) model, when CF is activated maximum output is decreased to 6KVA (4.8KW). 

 

 

 

 

Summary of Contents for (UL)

Page 1: ...10K UL www xmart ups com VER 190731 GA2UL ENG 1 VER 1907 31 ENGLISH USER MANUAL OPTIMA T10 6K 10K UL UPS ONLINE DOUBLE CONVERSION TOWER OPTIMA T10 06K 230V UL OPTIMA T10 10K 230V UL OPTIMA T10 06K IS...

Page 2: ...d or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without further notice XMART is not responsible of mistakes or mi...

Page 3: ...SAFETY QUALITY AND PERFORMANCE STANDARDS 3 PRODUCT DESCRIPTION 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 START UP 9 ERROR ALARMS CODES TROUBLESHOOTING 1...

Page 4: ...Bracelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electric...

Page 5: ...TRANSPORTATION IEC EN 300019 2 2 Class 2 3 WARNING Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party responsible for c...

Page 6: ...cations This product has been designed to operate under hostile electrical conditions but offering a reliable performance with outstanding features and characteristics It is 100 compatible to operate...

Page 7: ...f electrical shock because high DC voltage External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS DC polarity of the Battery bank...

Page 8: ...to find voltage in input lines of the UPS so that a back feed failure could represent an electrical shock risk for the operator An effective back feed design must be able to open automatically all UPS...

Page 9: ...rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru...

Page 10: ...with the UPS DC voltage before making DC connections In case electrical information given by this manual does match with information provided by product labels user must consider information on labels...

Page 11: ...tput 3000W 6 KVA Max Nominal Current 33A Output Voltage 120Vac Output Voltage 120Vac ISOTX Wiring min 10AWG 6mm2 AC Breaker 80A Curve D Breaker per Output 40A Curve D Max Nominal Current 60A Max Nomin...

Page 12: ...s provide 3KVA maximum AC lines must be connected to electrical board using cables with required gauge INPUT OUTPUT CONNECTIONS First of all connect ground terminals to system earth Ground must always...

Page 13: ...parate 120Vac outputs that can be wired in 3 different configurations 2 individual outputs120V Each output can drive 50 of total UPS power 1 output 120V By connecting 2 separate outputs in parallel Th...

Page 14: ...rallel connection also allows system can grow in power by adding extra units For working parallel as a parallel system all units must share same AC input and AC output Some control cables must be also...

Page 15: ...ommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all UPS of the par...

Page 16: ...UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since...

Page 17: ...RTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all...

Page 18: ...rd UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always sinc...

Page 19: ...GA2UL ENG 19 CONTROL CABLES CONNECTION DIAGRAM Parallel system requires all UPS share some important control information by parallel control cables There are 2 kind of control cables SHARED CURRENT P...

Page 20: ...AC input on its terminals If bypass mode is not enabling UPS will simply light its LCD Outputs will keep powered off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitr...

Page 21: ...s powered by AC input service so any problem in main service will affect directly to the load PROCEDURE FOR ACTIVATING EXTERNAL BYPASS 1 Confirm bypass mode is allowed in UPS configuration Check input...

Page 22: ...feeds rectifier input UPS output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output indicator dis...

Page 23: ...UPS will not turn on ENTER When UPS is in configuration mode this key operates as ENTER OFF ESCAPE UPS TURN OFF Press for 2 seconds to turn UPS off SCAPE When UPS is in configuration mode this key ope...

Page 24: ...INFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also show...

Page 25: ...ed 5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Pow...

Page 26: ...y to navigate or changing parameters value ON ENTER Used as ENTER key to confirm modifications MUTE DOWN Used as key to navigate or changing parameters value AVAILABLE FUNCTIONS UNDER EACH OPERATION M...

Page 27: ...put frequency If ATO is selected output frequency will be set by input frequency read when UPS started by first time from 46 to 54 Hz will set to 50Hz from 56 to 64 Hz will set to 60Hz IMPORTANT 1 If...

Page 28: ...r any condition PAR 03 ENA Enable Bypass allowed in both manual and automatic DIS Disable Automatic Bypass allowed but manual is prohibited Set values with keys 09 MAXIMUM RUNTIME This function sets m...

Page 29: ...or increasing SUB for decreasing Set values with keys THIS FUNCTION ONLY WORKS IF UPS IS CONNECTED IN PARALLEL 17 CHARGER CURRENT ADJUSTMENT BOTTOM PARAMETER Charging current can be selected 1A 2A 3A...

Page 30: ...nci n de Convertidor de Frecuencia Desactivado ON ON Encendido OFF OFF Apagado ENA Enable Habilitado DIS Disable Des habilitado ATO Auto mode Modo Autom tico SUB Subtract Disminuir ADD Add Aumentar PA...

Page 31: ...Power input lines ON at electrical board by setting Circuit Breaker to ON 3 Put Battery Bank breaker to ON in case UPS has XBAT connected 4 Put AC INPUT Breaker to ON in UPS rear panel 5 LCD of UPS mu...

Page 32: ...ARALLEL UPS Check all previous requirements are complied If not do nott try to start ups parallel UPS 1 Check parallel UPS are powered OFF and turned OFF 2 Check all input breakers are in OFF position...

Page 33: ...tery backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 The...

Page 34: ...consequence of detecting 3 overloads in less than 30 minutes OR MBS cover REMOVED 1 beep s ALARMS ALARM CODES Battery Disconnected 01 Battery overvoltage 07 Los Battery 08 Overload at UPS output 09 F...

Page 35: ...etected at inverter output 24 COMMUNICATION CAN error 31 DESBALANCED CURRENT IN PARALLEL SYTEM 36 OVER TEMPERATURE 41 CPU COMMUNICATION ERROR 42 OVERLOAD Detected at UPS output 43 Overload on inverter...

Page 36: ...SOLUCION 01 02 03 04 11 12 13 24 6A 6B 6C 60 63 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its output If UPS starts up without problems...

Page 37: ...e Batteries are located inside of the UPS or in external battery cabinets Original batteries must be replaced by new batteries with same technology VRLA and specifications 12VDC and similar capacity i...

Page 38: ...tion service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out...

Page 39: ...uxiliary output IEC 220Vac 9 Parallel Control Ports Shared Current 3 AC Input Breaker 10 Parallel Control Ports Parallel Control 4 Maintenance Bypass Switch MBS 11 FAN Power stage 5 DC connector for e...

Page 40: ...recarga 90 Charging VDC Voltaje del cargador Floating Temperature Compensation Compensaci n Temp Shutdown battery Voltage Voltaje DC Apagado 50 mV 12V 9AH x 40 pcs 20pcs x 2 240VDC 4 H 90 3 5 H 90 12...

Page 41: ...CF function is activated El modo bypass se anula automaticamente cuando se activa la funci n CF N5 Recharing time based on previous full discharging cycle 10 to 20 min Tiempo de recarga basado en cic...

Page 42: ...INDEX USER MANUAL OPTIMA T10 6K 10K UL www xmart ups com VER 190731 GA2UL ENG 42 NOTAS...

Page 43: ......

Page 44: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Santiago de Chile 8330669 Chile CHILE...

Reviews: