CIRCUIT BREAKERS AND WIRING SELECTION
Breakers and gauge of the wires used in input and output lines must be rated to drive current values in Amps as indicated in below tables.
NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than suggested
values in this section, please follow local regulations. Below wire gauge values are based on 1999 NEC for individual copper cables at
30ºC room temperature.
OPTIMA-T10 6K/10K 230V
Table 1:
230V with direct output from inverter (without output ISOTX)
MODEL
INPUT
OUTPUT
230V
220Vac
220Vac
OPTIMA-T09W-06KVA
AC Breaker:
40A (Curve D)
AC Breaker:
40A (Curve D)
(6 KVA)
Max. Nominal Current:
33A
Max. Nominal Current:
30A
230V
Wiring (min. size):
10AWG (6 mm2)
Wiring (min. size):
10AWG (6 mm2)
OPTIMA-T09W-10KVA
AC Breaker:
63A (Curve D)
AC Breaker:
63A (Curve D)
(10 KVA)
Max. Nominal Current:
55A
Max. Nominal Current:
50A
230V
Wiring (min. size):
8AWG (10 mm2)
Wiring (min. size):
8AWG (10 mm2)
OPTIMA-T10 6K/10K ISOTX
Table 2:
OPTIMA-T10 ISOTX with isolated output from ISOTX. ISOTX provides 2 outputs 120Vac.
MODEL
INPUT
FULL OUTPUT: 100% N1*
SEPARATE OUTPUTS: 50% N2*
ISOTX
220Vac
120Vac x 1 output
120Vac x 2 outputs
OPTIMA-T09W-06KVA AC Breaker:
40A (Curve D)
Full Output Capacity:
6000W
Watts per Output:
3000W
(6 KVA)
Max. Nominal Current:
33A
Output Voltage:
120Vac
Output Voltage:
120Vac
ISOTX
Wiring (min.):
10AWG (6mm2)
AC Breaker:
80A (Curve D)
Breaker per Output:
40A (Curve D)
Max. Nominal Current:
60A
Max. Nominal Current:
30A
Wiring (min.):
6AWG (16 mm2)
Wiring (min.):
10AWG (6 mm2)
OPTIMA-T09W-10KVA AC Breaker:
63A (Curve D)
Unique Output Capacity:
10000W
Watts per Output:
5000W
(10 KVA)
Max. Nominal Current:
55A
Output Voltage:
120Vac
Output Voltage:
120Vac
ISOTX
Wiring (min.):
8AWG (10mm2)
AC Breaker:
125A (Curve D)
Breaker per Output:
63A (Curve D)
Max. Nominal Current:
100A
Max. Nominal Current:
50A
Wiring (min.):
3AWG (35 mm2)
Wiring (min.):
8AWG (10 mm2)
NOTE: If ISOTX is configured with 1 output 220Vac, wiring selection must be done as described in table 1.
N1*:
Configuration for 1 output 120Vac. Under this configuration 2 individual outputs L1 and L2 are connected to offer 1 output.
N2*:
Configuration with 2 separate 120Vac outputs. Each output can only provide 50% of rated UPS max power.
Check chapter that describes all possible output configurations for ISOTX model.
DC LINES: UPS TO EXTERNAL BATTERIES PACKS (XBAT)
This UPS could be connected to external Battery packs (named XBAT) to provide longer runtime under Battery mode. Original XMART
XBAT comes with its own DC cable and DC breaker located on rear panel. In case of using non original external battery packs, user must
install DC breaker between each XBAT and the UPS:
MODEL:
EXT. BATT (240Vdc)
230V & ISOTX
BREAKER & WIRING
(06 KVA)
Breaker: 50A DC (Curve C) / Wiring (min. size): 10 AWG (6 mm2)
(10 KVA)