background image

INDEX

 

USER MANUAL 

 OPTIMA-T10 6K/10K (UL) 

 

 

www.xmart-ups.com 

VER.190731-GA2UL (ENG)

 

 

4.

 

INSTALLATION 

 

This section of the manual includes installation procedure and instructions for this UPS series. Before doing installation, you must 

revise and understand sections related to safety and site conditions. 

 

 

SAFETY INSTRUCTIONS 

 

WARNING:  Before  revising  this  section, 

you  must  read  and  understand  very  well  section  1  of  this  manual:  “GENERAL  SAFETY 

INSTRUCTIONS”.

 

 

WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION 

 

REACH AND LIABILITY LIMITATION: 

The preparation of the site, wiring and all protection devices must be supplied by end user and it will 

not be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up. 

 

The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical 

requirements. 

 

This manual describes minimal conditions and technical requirements with which the site must accomplish. 

Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or normative. 

In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this manual. In that 

case end user electrical contractor must be sure to comply with all related local electrical regulations and directives. 

 

 

Installation and start-ups MUST be done by qualified personnel only complying with safety procedures. 

 

This kind of equipment has been designed to provide electrical output even when it is not powered-on. 

 

UPS output could be energized even when UPS is turned-off in case external bypass is activated. 

 

Internal or external battery banks always can generate risk of electrical shock because high DC voltage. 

 

External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS.    

 

DC polarity of the Battery bank must be revised to confirm it is OK before connection. A reverse polarity can generate permanent 

damage in batteries and UPS. 

 

This UPS is rated as “Class I” so it is recommendable to co

nnect GROUND terminal to the EARTH before making any other connections. 

 

Before making AC input connections, technicians must confirm all switches of input lines are in open state (OFF). 

 

All installation instructions of this manual must be complied. 

 

All local electrical regulations must be complied. 

 

Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity and technology 

appropriate to effectively accomplish its function. Moreover, installation grounding must be correct. 

 

Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures 

 

Do not connect to UPS equipment or devices that exceed its capacity, this would overload the UPS. 

 

This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature. 

 

Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation. 

 

This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS shows 

the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently. 

 

Do not connect AC motor-based equipment without a careful sizing of the UPS based on inrush current instead of average current. 

Inrush current typical of motor-based system could overload this UPS. 

 

We strongly recommend placing a warning sign on main electrical board to avoid external personnel manipulate AC lines during 

revision and start-up work is performed. 

 

 

 

Summary of Contents for (UL)

Page 1: ...10K UL www xmart ups com VER 190731 GA2UL ENG 1 VER 1907 31 ENGLISH USER MANUAL OPTIMA T10 6K 10K UL UPS ONLINE DOUBLE CONVERSION TOWER OPTIMA T10 06K 230V UL OPTIMA T10 10K 230V UL OPTIMA T10 06K IS...

Page 2: ...d or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without further notice XMART is not responsible of mistakes or mi...

Page 3: ...SAFETY QUALITY AND PERFORMANCE STANDARDS 3 PRODUCT DESCRIPTION 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 START UP 9 ERROR ALARMS CODES TROUBLESHOOTING 1...

Page 4: ...Bracelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electric...

Page 5: ...TRANSPORTATION IEC EN 300019 2 2 Class 2 3 WARNING Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party responsible for c...

Page 6: ...cations This product has been designed to operate under hostile electrical conditions but offering a reliable performance with outstanding features and characteristics It is 100 compatible to operate...

Page 7: ...f electrical shock because high DC voltage External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS DC polarity of the Battery bank...

Page 8: ...to find voltage in input lines of the UPS so that a back feed failure could represent an electrical shock risk for the operator An effective back feed design must be able to open automatically all UPS...

Page 9: ...rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru...

Page 10: ...with the UPS DC voltage before making DC connections In case electrical information given by this manual does match with information provided by product labels user must consider information on labels...

Page 11: ...tput 3000W 6 KVA Max Nominal Current 33A Output Voltage 120Vac Output Voltage 120Vac ISOTX Wiring min 10AWG 6mm2 AC Breaker 80A Curve D Breaker per Output 40A Curve D Max Nominal Current 60A Max Nomin...

Page 12: ...s provide 3KVA maximum AC lines must be connected to electrical board using cables with required gauge INPUT OUTPUT CONNECTIONS First of all connect ground terminals to system earth Ground must always...

Page 13: ...parate 120Vac outputs that can be wired in 3 different configurations 2 individual outputs120V Each output can drive 50 of total UPS power 1 output 120V By connecting 2 separate outputs in parallel Th...

Page 14: ...rallel connection also allows system can grow in power by adding extra units For working parallel as a parallel system all units must share same AC input and AC output Some control cables must be also...

Page 15: ...ommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all UPS of the par...

Page 16: ...UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since...

Page 17: ...RTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all...

Page 18: ...rd UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always sinc...

Page 19: ...GA2UL ENG 19 CONTROL CABLES CONNECTION DIAGRAM Parallel system requires all UPS share some important control information by parallel control cables There are 2 kind of control cables SHARED CURRENT P...

Page 20: ...AC input on its terminals If bypass mode is not enabling UPS will simply light its LCD Outputs will keep powered off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitr...

Page 21: ...s powered by AC input service so any problem in main service will affect directly to the load PROCEDURE FOR ACTIVATING EXTERNAL BYPASS 1 Confirm bypass mode is allowed in UPS configuration Check input...

Page 22: ...feeds rectifier input UPS output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output indicator dis...

Page 23: ...UPS will not turn on ENTER When UPS is in configuration mode this key operates as ENTER OFF ESCAPE UPS TURN OFF Press for 2 seconds to turn UPS off SCAPE When UPS is in configuration mode this key ope...

Page 24: ...INFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also show...

Page 25: ...ed 5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Pow...

Page 26: ...y to navigate or changing parameters value ON ENTER Used as ENTER key to confirm modifications MUTE DOWN Used as key to navigate or changing parameters value AVAILABLE FUNCTIONS UNDER EACH OPERATION M...

Page 27: ...put frequency If ATO is selected output frequency will be set by input frequency read when UPS started by first time from 46 to 54 Hz will set to 50Hz from 56 to 64 Hz will set to 60Hz IMPORTANT 1 If...

Page 28: ...r any condition PAR 03 ENA Enable Bypass allowed in both manual and automatic DIS Disable Automatic Bypass allowed but manual is prohibited Set values with keys 09 MAXIMUM RUNTIME This function sets m...

Page 29: ...or increasing SUB for decreasing Set values with keys THIS FUNCTION ONLY WORKS IF UPS IS CONNECTED IN PARALLEL 17 CHARGER CURRENT ADJUSTMENT BOTTOM PARAMETER Charging current can be selected 1A 2A 3A...

Page 30: ...nci n de Convertidor de Frecuencia Desactivado ON ON Encendido OFF OFF Apagado ENA Enable Habilitado DIS Disable Des habilitado ATO Auto mode Modo Autom tico SUB Subtract Disminuir ADD Add Aumentar PA...

Page 31: ...Power input lines ON at electrical board by setting Circuit Breaker to ON 3 Put Battery Bank breaker to ON in case UPS has XBAT connected 4 Put AC INPUT Breaker to ON in UPS rear panel 5 LCD of UPS mu...

Page 32: ...ARALLEL UPS Check all previous requirements are complied If not do nott try to start ups parallel UPS 1 Check parallel UPS are powered OFF and turned OFF 2 Check all input breakers are in OFF position...

Page 33: ...tery backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 The...

Page 34: ...consequence of detecting 3 overloads in less than 30 minutes OR MBS cover REMOVED 1 beep s ALARMS ALARM CODES Battery Disconnected 01 Battery overvoltage 07 Los Battery 08 Overload at UPS output 09 F...

Page 35: ...etected at inverter output 24 COMMUNICATION CAN error 31 DESBALANCED CURRENT IN PARALLEL SYTEM 36 OVER TEMPERATURE 41 CPU COMMUNICATION ERROR 42 OVERLOAD Detected at UPS output 43 Overload on inverter...

Page 36: ...SOLUCION 01 02 03 04 11 12 13 24 6A 6B 6C 60 63 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its output If UPS starts up without problems...

Page 37: ...e Batteries are located inside of the UPS or in external battery cabinets Original batteries must be replaced by new batteries with same technology VRLA and specifications 12VDC and similar capacity i...

Page 38: ...tion service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out...

Page 39: ...uxiliary output IEC 220Vac 9 Parallel Control Ports Shared Current 3 AC Input Breaker 10 Parallel Control Ports Parallel Control 4 Maintenance Bypass Switch MBS 11 FAN Power stage 5 DC connector for e...

Page 40: ...recarga 90 Charging VDC Voltaje del cargador Floating Temperature Compensation Compensaci n Temp Shutdown battery Voltage Voltaje DC Apagado 50 mV 12V 9AH x 40 pcs 20pcs x 2 240VDC 4 H 90 3 5 H 90 12...

Page 41: ...CF function is activated El modo bypass se anula automaticamente cuando se activa la funci n CF N5 Recharing time based on previous full discharging cycle 10 to 20 min Tiempo de recarga basado en cic...

Page 42: ...INDEX USER MANUAL OPTIMA T10 6K 10K UL www xmart ups com VER 190731 GA2UL ENG 42 NOTAS...

Page 43: ......

Page 44: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Santiago de Chile 8330669 Chile CHILE...

Reviews: