5 Start-up Operation
5.1 Start-up
Before beginning of start-up the wiring of the Controller including all field devices must be completely terminated!
After switching the power supply “ON” and the end of the Power On Time, then the Controller is ready for use.
The electrochemical sensor needs a warm up time of 1 hour.
The Controller is delivered with standard parameters and stages/set points. The assignment of the relays to the
individual stages must occur with start-up unless arrangements have been made with the factory for programming.
All other parameters are to be examined and adapted to the local conditions.
Specifications subject to change without notice. | USA 131119 | Page 24 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
Polygard® is a registered trademark of MSR | LGC/LG2-04
Specifications subject to change without notice. | USA 160104 | Page 24 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 200211 | Page 24 of 30
LGC-LG2 – UserManual