3.7.1 Service Mode
If the Service mode is set to (ON) then the stage/setpoints exceeded are not passed on to the assigned relays
during calibration or service work. The service mode is Reset automatically after 60 minutes or when the service
mode is set to off manually.
Symbol Description Default
Status
Function
Off
Service Mode Off
Off = Stages exceeded will activate the assigned relays
On = Stages exceeded will not activate the assigned relays
3.7.2 Software Version
Symbol Description Default
Status
Function
GC02-
XX
Software
Version
XX = Software Version
3.7.3 Maintenance Concept
The LGC/LG2-04 system monitors the maintenance intervals as required, by local Regulations or Customer
requirements
During startup and/or after maintenance the date for next maintenance is entered. When reaching this date on the
next morning at 9 o'clock the failure signal is activated and in the display the phone No. of the service technician is
displayed. The failure signal (maintenance) can be acknowledged by the operator. The maintenance message
(Service Phone No.) is reset after maintenance is accomplished and a new maintenance date is entered.
The service phone number can be individually entered in the next menu.
Symbol Description
Default
Status
Function
TT.MM.JJ Maintenance date
TT.MM.JJ = Input date for next maintenance.
0853....
Phone No.
Input the individual service phone No.
3.7.4 Average Function
The Controller calculates for each active sensing point the arithmetic average value from 10 measurements within
the time unit defined in the menu „ AV-time“. This average value is indicated in the menu “Sensor Readings” near
the current value. At each Sensor Point the control mode of current value or average value for the Stage/Setpoint
evaluation is defined.
The evaluation of the control mode average value is overlaid by the current value, if this exceeds Stage/Setpoint
defined in the menu „AV-Overlay”. The overlay is delayed by the time factor set in this menu.
Symbol Description Default
Status
Function
120 s
120pm
AV- Overlay 120 s
120 ppm
sec. = Delay time average value Overlay. 0 = No overlay Function
ppm = Threshold average Overlay
1800 s
AV-Time
1800 s
sec. = Time for calculate average value
3.7.5 Customer Password (Code 1)
Change the System Password for level 1
Symbol Description Default
Status
Function
1234
Customer-
password
1234
1234 = Define the Customer Password with 4 characters
Specifications subject to change without notice. | USA 131119 | Page 19 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
Polygard® is a registered trademark of MSR | LGC/LG2-04
Specifications subject to change without notice. | USA 160104 | Page 19 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 200211 | Page 19 of 30
LGC-LG2 – UserManual