Customer Services (858) 578-7887 & (888) GO IN
TEC
IN
TEC
Controls, 12700 Stowe Dr., Suite 1
0
0, Poway, CA 92064
Fax (858) 578-4633 & (888) FX IN
TEC
www.inteccontrols.com
Specification subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR
LGC/LG2-04
PolyGard
®
Multi-Point Controller
User Manual - LGC/LG2-04
Page 17
3.6.9 Assigned Stage to Relay
Each of the 5 alarms can be assigned to a freely selectable alarm relay
.
Alarms, those not to be needed do not
receive assignment.
Symbol Description
Default
Status
Function
SP 01
Sensor Point
Selection SP No.
1
A1
A2
A3
A4
A5
01
02
03
04
00
01 = Stage 1 activate relay R 01
02 = Stage 2 activate relay R 02
03 = Stage 3 activate relay R 03
04 = Stage 4 activate relay R 04
00 = Stage 5 does not activate any relay
0
A
0
0 = SP Signal not assigned to any analog output
1 = SP Signal assigned to analog output 1
X
= SP Signal assigned to analog output
X
3.6.10 Assigned SP Signal to analog Output
The sensor point signal can be assigned to one of the two analog Outputs. The signal defined in the control
mode (current or average value) is transmitted. The assignment occurs in the menu „assignment alarm < > alarm
relay” in the right place.
Analog output see also: 3.7.2
3.7 Menu System Setup
Display and change the System Parameters for the Controller
(Main Menu)
See 3.7.1
See 3.7.2
See 3.7.3
See 3.7.3
See 3.7.4
See 3.7.4
See 3.7.5
Software Version
GC02- XX
Next maint. Date
TT.MM.JJ
System Setup
Service Mode
OFF
Service Phone
858 578-7887
AV Overlay
0 s. 120 ppm
AV Time
1800 s
Time system
US
Specifications subject to change without notice. | USA 131119 | Page 17 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
Polygard® is a registered trademark of MSR | LGC/LG2-04
Specifications subject to change without notice. | USA 160104 | Page 17 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 200211 | Page 17 of 30
LGC-LG2 – UserManual